Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: IN PHAZE ELECTRIC INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of IN PHAZE ELECTRIC INC in 2100 CONSULATE DR, ORLANDO, FL 32837 (NAICS 238210). OSHA activity number 346458078.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch In Phaze Electric INC — free Get an email when a new federal OSHA severe-injury report for In Phaze Electric INC is published. One employer, no account, unsubscribe in one click.
Site address
2100 CONSULATE DR
City
ORLANDO
State
FL
ZIP
32837
Mailing
10139 RIVERS TRAIL DRIVE, ORLANDO, FL 32817
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
22
Ownership type
A

2 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2023
Penalty
Initial $6,250 · Current $4,375 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee would be exposed were not deenergized before the employee worked on or near them, and the employer did not demonstrate that deenergizing introduced additional or increased hazards or was infeasible due to equipment design or operational limitations:  a.) On or about January 23, 2023 at Costech Labs, employees were exposed to the hazards of electrical shock and arc flash while installing approximately 50 feet of EMT conduit and wiring to connect a piece of equipment to a 200 amp breaker in a 480 V, 800 amp switchgear without de-energizing the switchgear.
Recent events (2)
  • — I (S) $4375
  • — Z (S) $6250

1910.335 A02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2023
Abate by
Sep 29, 2023
Penalty
Initial $6,250 · Current $4,375 Reduced
29 CFR  1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:  a) On or about January 23, 2023 at Costech Labs, two employees were exposed to the hazards of electrical shock and arc flash while installing approximately 50 feet of EMT conduit and wiring to connect a piece of equipment to a 200 amp breaker in a 480 V, 800 amp switchgear without de-energizing the switchgear and while using uninsulated tools such as pliers.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification.  This documentation may include but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $4375
  • — Z (S) $6250

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346458078.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.