FORT CAMPBELL, KY —
OSHA Inspection: U.S. DEPT. OF THE ARMY
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of U.S. DEPT. OF THE ARMY in BLDG 3902 INDIANA AVE HVAC SYSTEM FACILITY, FORT CAMPBELL, KY 42223 (NAICS 928110). OSHA activity number 346459084.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPT. OF THE ARMY
- Site address
- BLDG 3902 INDIANA AVE HVAC SYSTEM FACILITY
- City
- FORT CAMPBELL
- State
- KY
- ZIP
- 42223
- Mailing
- BLDG 6074 SCREAMING EAGLE BLVD, FORT CAMPBELL, KY 42223
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 1
- Ownership type
- D
Citations
13 citations on file for this inspection.
1910.36 A02
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(a)(2): An exit must be separated by fire resistant materials. Construction materials used to separate an exit from other parts of the workplace must have a one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour fire resistance-rating if the exit connects four or more stories. (a)Bldg. 3902, employee breakroom/office, South wall: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit door required to have a fire rating was rendered ineffective by the removal of the door knob leaving an open hole.
Recent events (1)
- — Z (S) $0
1910.36 E02
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(e)(2): The door that connects any room to an exit route must swing out in the direction of exit travel if the room is designed to be occupied by more than 50 people or if the room is a high hazard area (i.e., contains contents that are likely to burn with extreme rapidity or explode). (a)Bldg. 3902, employee breakroom/office, South wall: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit door required to swing outwards is hinged to swing inwards.
Recent events (1)
- — Z (S) $0
1910.37 B06
- Issued
- Jul 5, 2023
- Abate by
- Jul 24, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: (a)Bldg. 3902, employee breakroom/office, South wall: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit sign was not illuminated or a distinctive color. (b)Bldg. 3902, hallway between employee breakroom/office and outside egress: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit sign was not illuminated or a distinctive color.
Recent events (1)
- — Z (S) $0
1910.37 B07
- Issued
- Jul 5, 2023
- Abate by
- Jul 24, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(7): Each exit sign must have the word "Exit" in plainly legible letters not less than six inches (15.2 cm) high, with the principal strokes of the letters in the word "Exit" not less than three-fourths of an inch (1.9 cm) wide. (a)Bldg. 3902, employee breakroom/office, South wall: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit sign was hand written on a door using black marker in letters that were too small. (b)Bldg. 3902, hallway between employee breakroom/office and outside egress: On or about January 25th 2023 the employer exposed employees to death or serious injury from fire hazards in that an exit sign was hand written on a door using black marker in letters that were too small.
Recent events (1)
- — Z (S) $0
1910.102 A
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.102(a): The employer did not ensure that the in-plant transfer, handling, storage, and use of acetylene in cylinders complied with the provisions of CGA Pamphlet G-1-2009 ("Acetylene"), which is incorporated by reference as specified in 29 CFR 1910.6: (a) On or about January 25th, 2023 in Bldg. 3902, center of main floor, West side of chillers: employees were exposed to fire hazards and struck by hazards due to acetylene cylinder tanks being stored unsecured, and employer did not ensure that CGA Pamphlet G-1-2009 was followed as it includes in 6.1, "When moving acetylene cylinders, as in storing them, it is important to remember that they should not be subjected to abnormal mechanical shocks that might damage the cylinders, the valve, or the fusible metal pressure relief devices."
Recent events (1)
- — Z (S) $0
1910.253 B04 III
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least 1 hour (a)Bldg. 3902, South-West side of main room, vicinity of industrial chillers and storage cabinet: employer exposed employees to explosive and fire hazards, in that an oxygen cylinder was stored next to an acetylene cylinder and in close proximity to flammable chemicals
Recent events (1)
- — Z (S) $0
1910.303 B07 IV
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. (a)North side of main room, bldg. 3902: employee exposed employees to electrocution hazards in that a live receptacle, used by employees to plug in power tools and fans, was allowed to deteriorate by corrosion by exposure to chemicals and moisture used in close proximity.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a)Electrical room, South side of building 3902, center panel box: employer exposed employees to electrocution and fire hazards in that the labeling inside the panel box door that listed the purpose of each disconnecting device was faded and unreadable.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a)Upstairs loft, South-East side of building 3902; employees were exposed to death or serious injury in that a flexible cord was used as permanent wiring to provide power to an AC Air Handler through a 110V receptacle.
Recent events (1)
- — Z (S) $0
1910.334 B02
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(b)(2): The repetitive manual reclosing of circuit breakers or reenergizing electric power and lighting circuits through replaced fuses was not prohibited: (a)Loft in South-East corner of bldg. 3902: On or about January 25th 2023, and at times prior, the employer exposed employees to possible fire and electrical hazards in that a zip tie was used to keep closed a circuit breaker that was tripping due to a load in excess of what the breaker was intended to carry, caused by a flexible cord being spliced into an air handler (see citation 1-8).
Recent events (1)
- — Z (S) $0
1910.22 A01
- Issued
- Jul 5, 2023
- Abate by
- Jul 24, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. (a) Pathway behind boilers is blocked by storage of boxes, ladders, and other materials (b) Pathway in electrical room is black by storage of wire and other electrical components to include combustible material
Recent events (1)
- — Z (O) $0
1910.141 G02
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.141(g)(2): Employees were permitted to consume food or beverage in area(s) exposed to toxic materials: (a) Kitchen area, East side of bldg. 3902: On or about January 25th 2023, and at times prior, the employer exposed employees to foodborne illnesses, contamination from chemicals, diseases from rodent feces, and insects, in that sanitary conditions were not maintained in the area where employees store and prepare food.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Jul 5, 2023
- Abate by
- Jul 24, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Bldg. 3902 East wall of main room: On or about 25 January 2023, and at times prior, the employer exposed employees to possible shock hazards in that junction boxes and fittings were missing covers or the covers were not properly attached. (b) Bldg. 3902 employee breakroom/office on East wall: On or about 25 January 2023, and at times prior, the employer exposed employees to possible shock hazards in that junction boxes and fittings were missing covers or the covers were not properly attached. (c) Bldg. 3902, South wall, vicinity of chiller 2: On or about 25 January 2023, and at times prior, the employer exposed employees to possible shock hazards in that junction boxes and fittings were missing covers or the covers were not properly attached. (d) Bldg. 3902, North wall, vicinity of center exit: On or about 25 January 2023, and at times prior, the employer exposed employees to possible shock hazards in that junction boxes and fittings were missing covers or the covers were not properly attached.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Dept. of the Army