FORT CAMPBELL, KY —
OSHA Inspection: U.S. DEPT. OF THE ARMY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPT. OF THE ARMY in 3709 POLK RD PRATT MUSEUM(BLDG 5702), FORT CAMPBELL, KY 42223 (NAICS 928110). OSHA activity number 346464720.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. DEPT. OF THE ARMY
- Site address
- 3709 POLK RD PRATT MUSEUM(BLDG 5702)
- City
- FORT CAMPBELL
- State
- KY
- ZIP
- 42223
- Mailing
- BLDG 6074 SCREAMING EAGLE BLVD, FORT CAMPBELL, KY 42223
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 3
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.147 C07 I
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i):The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices: (a) On or about 01/26/2023, and at times prior, the employer exposed employees to an electrical hazard while conducting lock out tag out procedures on a breaker box with no knowledge/training.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) On or about 01/26/2023, and at times prior, the breaker panel for the Fort Campbell Museum had exposed openings exposing employees to an electrical hazard while conducting lock out tag out procedures on a breaker box.
Recent events (1)
- — Z (S) $0
1960.8 A
- Issued
- Jul 5, 2023
- Abate by
- Jul 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm: (a) On or about 01/26/2023, and at times prior, the employer exposed employees to an explosion/fire hazard while operating a Hurst mobile boiler (SN: FB200-30-8M) that was installed on a combustible trailer.
Recent events (1)
- — Z (S) $0
More inspections at U.S. Dept. of the Army
View U.S. Dept. of the Army's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in KY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346464720.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.