OSHA Inspection: JEWELL ELECTRIC INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JEWELL ELECTRIC INC. in 100 HOSPITAL AVENUE, DUBOIS, PA 15801 (NAICS 238210). OSHA activity number 346485204.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jewell Electric INC. — free Get an email when a new federal OSHA severe-injury report for Jewell Electric INC. is published. One employer, no account, unsubscribe in one click.
Site address
100 HOSPITAL AVENUE
City
DUBOIS
State
PA
ZIP
15801
Mailing
7 WEST LOGAN AVENUE, DUBOIS, PA 15801
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

8 citations on file for this inspection.

1926.416 A01

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $8,438 · Current $5,375 Reduced
29 CFR  1926.416(a)(1):The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work:   a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, An employee was working inside an energized 208V DPEM transfer switch in the basement electrical room. The employee received an electrical shock which required another employee to reach inside the energized switchgear for rescue purposes.
Recent events (2)
  • — I (S) $5375
  • — Z (S) $8438

1926.417 B

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.417(b): Equipment or circuits that were de-energized were not rendered inoperative:   a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, an employee was working inside an energized 208V DPEM transfer switch in the basement electrical room. The DPEM Transfer Switch#5 208V electrical Switchgear was not rendered inoperative prior to employees working inside the electrical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.21 B02

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $8,438 · Current $5,375 Reduced
29 CFR  1926.21(b)(2):The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:  a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, an employee was working in an energized 208V DPEM transfer switch switchgear. The employee had not been instructed in the electrical safety related work practices and/or the requirements noted in NFPA70E prior to starting the electrical work.  b.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, personnel were potentially exposed to electrical hazards while working on, with, and around live electrical equipment and were not trained on the requirements of 29CFR 1926.417 (i.e. Electrical Lockout/Tagout).  c.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, and at times prior thereto, personnel were potentially exposed to electrical hazards while working on, with, and around live electrical equipment and were not trained on the requirements of 29CFR 1926.416 (i.e. Safe Work Around Electrical Systems).
Recent events (2)
  • — I (S) $5375
  • — Z (S) $8438

1926.20 B02

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s).  a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, an inspection or evaluation of the job site and electrical equipment was not conducted by a competent person prior employees conducting work inside an energized 208V DPEM transfer switch switchgear.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.20 B01

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.20(b)(1): The employer did not initiate and maintain such programs as may be necessary to comply with this part.   a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, A safety and health program element was not developed or implemented for electrical safe work practices.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.95 A

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $8,438 · Current $5,375 Reduced
29 CFR  1926.95(a):Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:  a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, an employee was working in the 208V DPEM transfer switch switchgear  while it was energized without electrical personal protective equipment in the basement electrical room. Employees did not have the appropriate arc flash personal protective equipment available to perform the work. Missing personal protective equipment include, but is not limited to; arc flash gloves, face shield, and suit.
Recent events (2)
  • — I (S) $5375
  • — Z (S) $8438

1926.97 C02 VIII

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.97(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5.   a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, rubber insulating arc flash gloves available for employee use exceeded the maximum intervals between tests. The gloves available to employees had an inspection date of September 28, 2017.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.416 A03

Serious Gravity 5 1 instance 2 exposed
Issued
May 23, 2023
Abate by
Jul 24, 2023
Penalty
Initial $8,438 · Current $5,375 Reduced
29 CFR  1926.416(a)(3):The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take.   a.) Jewell Electric Inc.; 100 Hospital Ave Dubois, Pa 15801- On or about 02/06/2023 and at times prior thereto, an employee was removing electrical components including, but not limited to, fire pump wiring inside the energized 208V DPEM transfer switch switchgear in the basement electrical room. While removing the wires, the employee contacted an unknown energized source inside the 208V switchgear. The entire electrical system was not thoroughly metered with instrumentation to determine whether any part of an energized electric power circuit was present in the area where the employee was working. After the accident, it was determined that terminals were energized inside the DPEM switchgear.
Recent events (2)
  • — I (S) $5375
  • — Z (S) $8438

View Jewell Electric INC.'s full OSHA safety record →