Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. POSTAL SERVICE - VASHON

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of U.S. POSTAL SERVICE - VASHON in 10005 SOUTHWEST 178TH STREET, VASHON, WA 98070 (NAICS 491110). OSHA activity number 346496821.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Postal Service - Vashon — free Get an email when a new federal OSHA severe-injury report for U.S. Postal Service - Vashon is published. One employer, no account, unsubscribe in one click.
Site address
10005 SOUTHWEST 178TH STREET
City
VASHON
State
WA
ZIP
98070
Mailing
10005 SOUTHWEST 178TH STREET, VASHON, WA 98070
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
491110
Employees
6
Ownership type
A

2 citations on file for this inspection.

1910.304 B04 II B

Other-than-serious Gravity 1 1 instance 15 exposed
Issued
Apr 17, 2023
Abate by
May 11, 2023
Penalty
Initial $7,366 · Current $3,683 Reduced
29 CFR  1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4:  A) In the break room of the postal facility, there was a power strip with 15 amp outlets that was plugged into a 15 amp wall outlet that ran on a 20 amp branch circuit. There was a 1500 watt (12.5) amp microwave oven and a 1000 watt (8.3 amp) coffee maker plugged into the power strip, potentially running a 20.8 amp load through outlets that were rated for a maximum of 15 amps. This could result in overheating of the fixtures and cause a fire.
Recent events (2)
  • — I (O) $3683
  • — Z (S) $7366

1910.305 C04

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 17, 2023
Abate by
May 11, 2023
Penalty
Initial $7,366 · Current $5,156 Reduced
29 CFR  1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have a faceplate installed so as to completely cover the opening and seat against the finished surface.  A)     In the entry to the loading dock of the postal facility there was an electrical fixture box that had 4 switches.  The corner of the faceplate was broken exposing the inner electrical components.  This could result in and contamination or deterioration of the wiring, which can cause fire.
Recent events (2)
  • — I (S) $5156.2
  • — Z (S) $7366