Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KRUSE & KAMIEN SCHALTANLAGEN GMBH

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of KRUSE & KAMIEN SCHALTANLAGEN GMBH in 1125 COUNTY ROAD 1A, IRONTON, OH 45638 (NAICS 238210). OSHA activity number 346523418.

Watch Kruse & Kamien Schaltanlagen Gmbh — free Get an email when a new federal OSHA severe-injury report for Kruse & Kamien Schaltanlagen Gmbh is published. One employer, no account, unsubscribe in one click.
Site address
1125 COUNTY ROAD 1A
City
IRONTON
State
OH
ZIP
45638
Mailing
GELBER DAMM 11
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

4 citations on file for this inspection.

1926.20 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 13, 2023
Abate by
Jul 11, 2023
Penalty
Initial $4,688 · Current $4,688
29 CFR  1926.20(b)(2): Such programs shall provide for frequent and regular inspections of the job sites, materials, and equipment to be made by competent persons designated by the employers.    On or about 01/29/2023, the employer did not ensure that a frequent and regular inspections were being conducted by a competent person designated by Kruse & Kamien Schaltanlagen GmbH at 1125 County Road 1A Ironton, OH 45638 to ensure that the job site, material and equipment; such as but not limited to the Fluke 77IV Multimeter was not adjusted to remove the fuse and allow employees to contact an energized 480V energy source located in the newly installed Electrical Cabinet (PK720/PK730) at PureCycle Ohio. The hazard last occurred on February 15, 2023.
Recent events (1)
  • — Z (S) $4688

1926.21 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 13, 2023
Abate by
Jul 11, 2023
Penalty
Initial $4,688 · Current $4,688
29 CFR  1926.21(b)(2): The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.    a) On or about 01/29/2023, Kruse & Kamien Schaltanlagen GmbH (employer) working at site location 1125 County Road 1A Ironton, OH 45638, did not ensure that employees were instructed in the recognition and avoidance of unsafe conditions, specifically with arc flash and electrical hazards, while working  on an energized 480V energy source located in the newly installed Kruse and Kamien Schaltanlagen GmbH Electrical Cabinets (PK720/PK730) at PureCycle Ohio with a modified Fluke 77IV Multimeter. The hazard last occurred on February 15, 2023.
Recent events (1)
  • — Z (S) $4688

1926.95 A

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 13, 2023
Abate by
Jul 11, 2023
Penalty
Initial $4,688 · Current $4,688
29 CFR  1926.95(a):"Application." Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, shall be provided, used, and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact.  a) On or about 02/15/2022, the employer did not ensure that employees working on testing voltage, with a modified Fluke 77IV Multimeter,  on an energized 480 volt power supply to a circuit breaker inside of a newly installed, Kruse and Kamien manufactured electrical cabinet used electrical protective equipment that would have been appropriate to protect employees from potential exposure to arc flash hazards.
Recent events (1)
  • — Z (S) $4688

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jun 13, 2023
Abate by
Jul 11, 2023
Penalty
Initial $4,688 · Current $4,688
29 CFR  1926.416(a)(1): No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.   a) On or about 01/29/2023, the employer did not ensure that employees whose duties were to test voltage, with a Fluke 77IV Multimeter,  for an energized 480 volt power supply to a circuit breaker after installing a Kruse and Kamien manufactured electrical cabinet were protected against electric shock by guarding it effectively by insulation or other means. This last occurred on 02/15/2023.
Recent events (1)
  • — Z (S) $4688

LIPPERT

PROVIA

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346523418.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.