OKLAHOMA CITY, OK —
OSHA Inspection: BOARDMAN, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BOARDMAN, INC. in 1135 S. MCKINLEY, OKLAHOMA CITY, OK 73108 (NAICS 332313). OSHA activity number 346527302.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BOARDMAN, INC.
- Site address
- 1135 S. MCKINLEY
- City
- OKLAHOMA CITY
- State
- OK
- ZIP
- 73108
- Mailing
- 1135 S. MCKINLEY, OKLAHOMA CITY, OK 73108
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332313
- Employees
- 59
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.134 C04
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $6,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.134(c)(4): The employer did not provide respirators, training, and medical evaluations at no cost to employees: On or about June 1, 2023 and at times prior to, employees required to wear respiratory protection were not provided with training, respiratory protection and/or medical evaluations at no cost, exposing employees to respiratory and inhalation hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $6250
1910.212 A01
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $10,938 · Current $0 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding were not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about February 6, 2023, at the large plate roller, employees are not protected from rotating parts when aligning plates, exposing the employees to caught-in hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $10938
1910.243 B02
- Issued
- Jun 30, 2023
- Penalty
- Initial $7,813 · Current $4,500 Reduced
General-duty citation text
29 CFR 1910.243(b)(2): Airhose and hose connections used for conducting compressed air to utilization equipment was not designed for the pressure and service to which they were subjected: On or about February 6, 2023, radiator style clamps were used to connect pneumatic lines to tools and other equipment, exposing employees to struck by hazards.
Recent events (2)
- — I (O) $4500
- — Z (S) $7813
1910.305 A01 I
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $7,813 · Current $4,500 Reduced
General-duty citation text
29 CFR 1910.305(a)(1)(i):Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and noncurrent-carrying parts that are to serve as grounding conductors, with or without the use of supplementary equipment grounding conductors, were not effectively bonded where necessary to ensure electrical continuity and did not have the capacity to conduct safely any fault current likely to have been imposed on them: On or about February 6, 2023, a metal raceway that was once attached to an electrical outlet was observed broken and detached from the outlet while the internal wirings were still attached, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $4500
- — Z (S) $7813
1910.305 B01
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: On or about February 6, 2023, unused openings in electrical outlet was not effectively closed, exposing employees to the hazard of electrical shock.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $7,813 · Current $4,500 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about February 6, 2023, extension cords were observed being used as a substitute for fixed wiring at the facility, when extension cords were observed zip tied to beams and other fixtures at the facility, exposing employees to electrical hazards.
Recent events (2)
- — I (O) $4500
- — Z (S) $7813
1910.22 A03
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3):Walking-working surfaces were not maintained free of hazards such as sharp or protruding objects, loose boards and general slip or trip hazard. On or about February 6, 2023, at the facility, metal plates that were once secured to the floor were detached extending 1-2 inches above the walking surface, exposing employees to tripping hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.101 B
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $877 · Current $500 Reduced
General-duty citation text
29 CFR 1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Compressed gas cylinders were not stored in accordance with Compressed Gas Association Pamphlet P-1-1965. This violation was observed on or about February 6, 2023, at the facility when compressed gas cylinders were not secured or provided with protective caps at the facility. Employees were exposed to fire, explosion, and struck by hazards.
Recent events (2)
- — I (O) $500
- — Z (O) $877
1910.157 C01
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: On or about February 6, 2023, at the facility, a fire extinguisher was observed mounted without marking illustrating the location of the fire extinguisher.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.254 D09 III
- Issued
- Jun 30, 2023
- Abate by
- Jul 27, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.254(d)(9)(iii): Cables with damaged insulation or exposed bare conductors were not replaced: On or about February 6, 2023, at the facility, welding cables with exposed copper wires were observed by the plate rollers, exposing employees to burns and shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Boardman, INC.
View Boardman, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332313)
More inspections in OK
Source