Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PIKES PEAK CHRISTIAN SCHOOL

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PIKES PEAK CHRISTIAN SCHOOL in 5905 FLINTRIDGE DR, COLORADO SPRINGS, CO 80918 (NAICS 611110). OSHA activity number 346537806.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pikes Peak Christian School — free Get an email when a new federal OSHA severe-injury report for Pikes Peak Christian School is published. One employer, no account, unsubscribe in one click.
Site address
5905 FLINTRIDGE DR
City
COLORADO SPRINGS
State
CO
ZIP
80918
Mailing
5905 FLINTRIDGE DR, COLORADO SPRINGS, CO 80918
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611110
Employees
68
Ownership type
A

4 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 7, 2023
Abate by
Jun 27, 2023
Penalty
Initial $10,938 · Current $7,000 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on  them:  (a)5905 Flintridge Drive, Colorado Springs CO., On or about 2/24/2023, and at times prior,  the employer, Pikes Peak Christian School, did not ensure that employees conducting electrical work, deenergized the fuse panel before performing work on it. The fuse panel contained three Bussman FRS-R-60, 60A, Class RK5 Fuses rated at 60 amps/600V which needed to be removed and replaced.  An employee sustained electrical burns to the face, torso, and arms as a result of an arc flash while attempting to remove the fuses while the panel was energized with uninsulated metal vice grip pliers.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $10938

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 7, 2023
Abate by
Jun 27, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:   (a) 5905 Flintridge Drive, Colorado Springs CO., On or about 2/24/2023, and at times prior, the employer, Pikes Peak Christian School, exposed employees to electrical hazards. The employer did not train employees assigned to perform electrical work on the safety related work practices necessary to perform the work in a safe manner. A non-qualified employee was attempting to remove a fuse from an energized fuse panel which contained three Bussmann FRS-R-60, 60A, Class RK5 Fuses: rated at 60 amps/600V. The employee sustained electrical burns to the face, torso, and arms as a result of an arc flash while attempting to remove the fuses with uninsulated metal vice grip pliers.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 7, 2023
Abate by
Jun 27, 2023
Penalty
Initial $10,938 · Current $7,000 Reduced
29 CFR  1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  (a) 5905 Flintridge Drive, Colorado Springs CO., On or about 2/24/2023, and at times prior, the employer, Pikes Peak Christian School, did not ensure employees were provided with electrical protective equipment while changing out three (3) energized Bussman FRS-R-60, 60A Fusetron Dual Element Class RK5 fuses, rated at 600V. Employees were exposed to electrical hazards in that an employee sustained electrical burns to his face, torso, and arms, as a result of an arc flash.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $10938

1910.335 A02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 7, 2023
Abate by
Jun 27, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(2)(i):When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:  (a) 5905 Flintridge Drive, Colorado Springs CO., On or about 2/24/2023, and at times prior, the employer Pikes Peak Christian School exposed employees to electrical hazards in that no insulated tools were used or provided to employees while attempting to change out three (3) energized Bussmann FRS-R-60, 60A, Class RK5 fuses rated at 60 amps/600V from a fuse box. The fuses were removed with uninsulated metal vice grip pliers resulting in an arc flash. An employee sustained  electrical burns to his face, torso and arms.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346537806.