Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VERSUM MATERIALS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of VERSUM MATERIALS in 12100 SAMSUNG BLVD. FAB 2 CHEMICAL SOLVENT ROOM, AUSTIN, TX 78754 (NAICS 334310). OSHA activity number 346585094.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Versum Materials — free Get an email when a new federal OSHA severe-injury report for Versum Materials is published. One employer, no account, unsubscribe in one click.
Establishment
VERSUM MATERIALS
Site address
12100 SAMSUNG BLVD. FAB 2 CHEMICAL SOLVENT ROOM
City
AUSTIN
State
TX
ZIP
78754
Mailing
12100 SAMSUNG BLVD. FAB 2 CHEMICAL SOLVENT ROOM, AUSTIN, TX 78754
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334310
Employees
172
Ownership type
A

1 citation on file for this inspection.

1910.119 J02

Other-than-serious Gravity 10 9 instances 4 exposed
Issued
Aug 23, 2023
Abate by
Sep 19, 2023
Penalty
Initial $14,063 · Current $8,438 Reduced
29 CFR 1910.119(j)(2): The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment.  On or about March 21, 2023, and at times prior, at the Austin Semiconductor facility in Austin, Texas, the employer did not develop written procedures for one- and two-year testing and inspecting including, but not limited to the following safety systems:  a. PT-1A (DEV-0000125) b. Independent TE (DEV-0000155) c. High-High Temperature TSHH-6 (DEV-0000155) d. PT1 (DEV-0000192) e. PT2(LL) (DEV-0000192) f. Excess Flow Switch/logic (DEV-0000192) g. PT-10(DEV-0000033) HCL h. PT-09(DEV-0000033) HCL i. PSHH-2 (DEV-000089  This exposed employees to fire and explosion hazards in the event of a release.
Recent events (2)
  • — I (O) $8437.8
  • — Z (S) $14063

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346585094.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.