TORRINGTON, CT —
OSHA Inspection: BOMAR SPECIALTIES, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BOMAR SPECIALTIES, LLC in 51 GREENWOODS ROAD, TORRINGTON, CT 06790 (NAICS 325211). OSHA activity number 346607583.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BOMAR SPECIALTIES, LLC
- Site address
- 51 GREENWOODS ROAD
- City
- TORRINGTON
- State
- CT
- ZIP
- 06790
- Mailing
- 318 INDUSTRIAL LANE, TORRINGTON, CT 06790
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325211
- Employees
- 16
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.178 C02 IV
- Issued
- May 30, 2023
- Abate by
- Sep 30, 2024
- Penalty
- Initial $3,036 · Current $2,125 Reduced
General-duty citation text
29 CFR 1910.178(c)(2)(iv): Power-operated industrial trucks designated as DY, EE, or EX were not used in locations where volatile flammable liquids or flammable gases were handled, processed or used, but in which the hazardous liquids, vapors or gases were normally confined within closed containers or closed systems from which they could escape only in case of accidental rupture or breakdown of such containers or systems, or in the case of abnormal operation of equipment: Warehouse: On, or about, April 3, 2023, E-rated forklift trucks were used to transport 55 gallon drums of Methyl ethyl ketone (MEK), a Category 2 flammable liquid, to and from the reactor rooms and to place and retrieve the drums from the racking system. In the event of a spill or rupture of a drum of MEK, the forklift trucks would be a potential ignition source.
Recent events (4)
- — P (S) $2125.2
- — I (S) $2125.2
- — P (S) $2125.2
1910.303 B01 II
- Issued
- May 30, 2023
- Abate by
- Sep 29, 2023
- Penalty
- Initial $4,554 · Current $3,188 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: Warehouse, Aisle D: On, or about, April 3, 2023, barrels that were being placed onto or retrieved from the storage racks came within inches of a live, 480 volt buss bar. The buss bar enclosure was not protected from physical damage.
Recent events (3)
- — I (S) $3187.8
- — P (S) $3187.8
- — Z (S) $4554
1910.303 G01 I A
- Issued
- May 30, 2023
- Penalty
- Initial $1,935 · Current $1,355 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Warehouse, Aisle D: On, or about, April 3, 2023, a barrier was installed in front of two General Electric Load Centers, Panels P and K. The barrier was located in the working space for the panels.
Recent events (2)
- — I (S) $1354.5
- — Z (S) $1935
1910.178 P01
- Issued
- May 30, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(p)(1): Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been taken out of service until restored to safe operating condition(s): Warehouse: On, or about, April 3, 2023, the battery provided on the #3 Toyota forklift was leaking acid solution. The acid had dried and caked on the surface of the battery.