EL PASO, TX —
OSHA Inspection: TEMP GLASS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TEMP GLASS INC. in 12 ZANE GREY STREET # A, EL PASO, TX 79906 (NAICS 327215). OSHA activity number 346670516.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TEMP GLASS INC.
- Site address
- 12 ZANE GREY STREET # A
- City
- EL PASO
- State
- TX
- ZIP
- 79906
- Mailing
- 12 ZANE GREY STREET # A, EL PASO, TX 79906
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327215
- Employees
- 37
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.147 C04 II B
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $8,438 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(B): Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy; On or about May 02, 2023, the employer did not establish specific procedural steps for shutting down, isolating, blocking and securing a polishing machine located in the cutting area, in order to control hazardous energy. This condition exposed employees to safety hazards.
Recent events (2)
- — I (S) $5000
- — Z (S) $8438
1910.303 B02
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $7,032 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about May 2, 2023, a relocatable power tap (power strip) located in the rhino area was used as a permanent receptacle and was not used in accordance with instructions in the listing or labeling. This condition exposed employees to an electrical shock hazard.
Recent events (2)
- — I (S) $4000
- — Z (S) $7032
1910.303 G01 I B
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $4,218 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment that is likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 30 inches, whichever was greater. On or about May 02, 2023, an electrical panel located in the cutting area was obstructed by a piece of cardboard and not accessible in the event of an emergency shutdown. This condition potentially exposed employees to fire and electrical hazards.
Recent events (2)
- — I (S) $1500
- — Z (S) $4218
1910.305 J02 IV
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $5,625 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location shall be suitable for the location. On or about May 02, 2023, an extension cord connected to a relocatable power tap (RPT) located in the cutting area, was directly above a wet or damp location. This condition exposed employees to an electrical shock hazard.
Recent events (2)
- — I (S) $2000
- — Z (S) $5625
1910.335 B01
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $5,625 · Current $2,000 Reduced
General-duty citation text
29 CFR 1910.335(b)(1): 29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them: On or about May 02, 2023, the employer did not ensure the proper labeling of electrical panels located in the compressed gas area. This condition exposed employees to electrical shock hazards.
Recent events (2)
- — I (S) $2000
- — Z (S) $5625
1910.157 C01
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $789 · Current $300 Reduced
General-duty citation text
29 CFR 1910.157(c)(1):The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury. On or about May 02, 2023, the employer did not ensure that the provided portable fire extinguishers were mounted and readily accessible to employees. This condition exposed employees to fire hazards in the following instances. 1. One fire extinguisher located in the Washing/ Cutting Area was not mounted and readily accessible to employees. 2. Two fire extinguishers located in the Oven Area were not mounted and readily accessible to employees.
Recent events (2)
- — I (O) $300
- — Z (O) $789
1910.303 B07 IV
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $789 · Current $300 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv):There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. On or about May 02, 2023, a damaged electrical control panel of a cooling system located in the oven area was kept closed with duct tape. This condition exposed employees to fire and electrical shock hazards.
Recent events (2)
- — I (O) $300
- — Z (O) $789
1910.305 B02 I
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $789 · Current $300 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about May 02, 2023, an indoor outlet box did not have a faceplate installed, located in the IG Line Area. This condition exposed employees to an electrical shock hazard.
Recent events (2)
- — I (O) $300
- — Z (O) $789
1910.305 H06
- Issued
- Sep 15, 2023
- Abate by
- Oct 4, 2023
- Penalty
- Initial $789 · Current $300 Reduced
General-duty citation text
29 CFR 1910.305(h)(6): Fittings. Connectors used to connect lengths of cable in a run shall be of a type that lock firmly together. Provisions shall be made to prevent opening or closing these connectors while energized. Strain relief shall be provided at connections and terminations. On or about May 02, 2023, an electrical wire located in the oven area was not used with a fitting that prevented a secure connection to be unfastened. This condition exposed employees to electrical shock hazards.
Recent events (2)
- — I (O) $300
- — Z (O) $789
More inspections at Temp Glass INC.
View Temp Glass INC.'s full OSHA safety record →
More inspections in this industry (NAICS 327215)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346670516.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.