Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: E LIGHT ELECTRIC SERVICES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of E LIGHT ELECTRIC SERVICES, INC. in 6363 SOUTH FIDDLERS GREEN CIRCLE, GREENWOOD VILLAGE, CO 80111 (NAICS 238210). OSHA activity number 346673312.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch E Light Electric Services, INC. — free Get an email when a new federal OSHA severe-injury report for E Light Electric Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
6363 SOUTH FIDDLERS GREEN CIRCLE
City
GREENWOOD VILLAGE
State
CO
ZIP
80111
Mailing
361 INVERNESS DRIVE SOUTH, SUITE B, ENGLEWOOD, CO 80112
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
140
Ownership type
A

2 citations on file for this inspection.

1926.416 A01

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Aug 28, 2023
Abate by
Dec 15, 2023
Penalty
Initial $14,063 · Current $6,000 Reduced
29 CFR  1926.416(a)(1):The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work:  (a)  6363 South Fiddler's Green Circle, Greenwood Village, CO 80111: On or about May 2, 2023, the employer E Light Electric Services, Inc., did not ensure its employees conducting a sub meter installation onto the main switchgear panel in an electrical room were protected from inadvertent contact with a live electrical source rated at 4000 amp/ 480v-660v. An employee sustained electrical burns to the face, neck and arms from an arc flash.
Recent events (3)
  • — F (O) $6000
  • — C (S) $14063
  • — Z (S) $14063

1926.417 A

Deleted Serious Gravity 10 1 instance 7 exposed
Issued
Aug 28, 2023
Abate by
Sep 22, 2023
Penalty
Initial $0 · Current $0
29 CFR  1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged:   (a)  6363 South Fiddler's Green Circle, Greenwood Village, CO 80111. On or about May 2, 2023, the employer, E light Electric Services, Inc., did not ensure its employees conducting a sub meter installation onto the main switchgear panel of an electrical room were protected from shock and electrical burns, in that the panel was energized and not locked or tagged out. An employee sustained electrical burns to the face, neck and arms from an arc blast.  After the incident,  additional employees were exposed to potential injury in that, the panel was de-energized; however, no locks or tags were placed on the controls to prevent reenergization.