OSHA Inspection: M.W. MOTORS INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of M.W. MOTORS INC. in 1921 OTSEGO AVENUE, COSHOCTON, OH 43812 (NAICS 441110). OSHA activity number 346689227.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch M.W. Motors INC. — free Get an email when a new federal OSHA severe-injury report for M.W. Motors INC. is published. One employer, no account, unsubscribe in one click.
Establishment
M.W. MOTORS INC.
Site address
1921 OTSEGO AVENUE
City
COSHOCTON
State
OH
ZIP
43812
Mailing
1921 OTSEGO AVENUE, COSHOCTON, OH 43812
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
441110
Employees
27
Ownership type
A

7 citations on file for this inspection.

1910.253 B04 III

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $7,813 · Current $0 Reduced
29 CFR  1910.253(b)(4)(iii): Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  a) On or about May 9, 2023, in the back shop, oxygen cylinders were not separated from acetylene fuel-gas cylinders by a minimum distance of 20 feet or by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one-half hour.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7813

1910.303 B02

Serious Gravity 1 2 instances 2 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $4,687 · Current $4,687
29 CFR  1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.  a)	On or about May 9, 2023, the employer did not ensure that extension cords being used to power two 4 ft LED double light fixtures and other equipment in bay 3, were used in accordance with instructions included in the listing or labeling. Extension cords were utilized in series into a power strip, thereby exposing employees to electrical and fire hazards.   b)	On or about May 9, 2023, the employer did not ensure that extension cords being used to power a 4 ft LED double light fixture in bay 1, were used in accordance with instructions included in the listing or labeling. Extension cords were utilized in series into another extension cord (daisy chained), thereby exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $4687
  • — Z (S) $4687

1910.305 B01 II

Serious Gravity 5 2 instances 3 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $6,250 · Current $6,250
29 CFR  1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.  a) On or about May 9, 2023, in the back shop, the employer did not ensure that an electrical panel with unused openings were effectively closed, thereby exposing employees to 120-volt electrical contact hazards.  b) On or about May 9, 2023, in the back shop, the employer did not ensure that an electrical receptacle box with unused openings were effectively closed, thereby exposing employees to 120-volt electrical contact hazards.
Recent events (2)
  • — I (S) $6250
  • — Z (S) $6250

1910.305 G01 IV A

Serious Gravity 5 2 instances 3 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $6,250 · Current $0 Reduced
29 CFR  1910.305(g)(1)(iv): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used:  29 CFR  1910.305(g)(1)(iv)(A): As a substitute for the fixed wiring of a structure;  a) On or about May 9, 2023, in the back shop, an extension cord was used to provide electricity to two 4 ft LED double light fixtures above bay 3. The flexible cords were used in lieu of fixed wiring, thereby exposing employees to electrical and fire hazards.  b) On or about May 9, 2023, in the back shop, an extension cord was used to provide electricity to a 4 ft LED double light fixture above bays 1 and  2. The flexible cords were used in lieu of fixed wiring, thereby exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6250

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $6,250 · Current $0 Reduced
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.  a) On or about May 9, 2023, the windshield washer fluid pump station did not have strain relief provided for its 120-volt flexible supply cord allowing wires to become visible, thereby exposing employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6250

1910.303 G01

Other-than-serious 1 instance 2 exposed
Issued
Jun 22, 2023
Abate by
Jul 11, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.  a) On or about May 9, 2023, in the back shop, electrical control panels that controlled automotive lifts, lights, etc. were obstructed by a transmission jack, cylinder hand truck, tires and other equipment, thereby preventing employees access in the event of an emergency.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.22 A03

Other-than-serious 2 instances 3 exposed
Issued
Jun 22, 2023
Abate by
Jul 27, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.22(a)(3): (3) Walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice.   a)	On or about May 9, 2023, located in the back shop, rainwater caused wet floors due to roof damage, thereby exposing employees to slip/trip hazards.