Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UPS INDUSTRIAL SERVICES, LLC

Programmed Related inspection · Safety discipline

On , OSHA opened a programmed Related safety inspection of UPS INDUSTRIAL SERVICES, LLC in 5900 HIGHWAY 225, DEER PARK, TX 77536 (NAICS 324110). OSHA activity number 346693369.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch UPS Industrial Services, LLC — free Get an email when a new federal OSHA severe-injury report for UPS Industrial Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
5900 HIGHWAY 225
City
DEER PARK
State
TX
ZIP
77536
Mailing
306 DEERWOOD GLEN DRIVE, DEER PARK, TX 77536
Inspection type
Programmed Related (J)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
15
Ownership type
A

4 citations on file for this inspection.

1910.119 H03 IV

Other-than-serious Gravity 10 2 instances 5 exposed
Issued
Sep 15, 2023
Abate by
Nov 2, 2023
Penalty
Initial $15,625 · Current $3,000 Reduced
29 CFR  1910.119(h)(3)(iv):The contract employer did not assure that each contract employee follows the safety rules of the facility including the safe work practices required by paragraph (f)(4) of this section. On or about May 5, 2023, employees were exposed to fire, explosion, and toxic gas release hazards when the designated craft worker (Supervisor) did not walkdown the electrical isolation of MOV-2516. Although Supervisor reviewed the master isolation list and confirmed the mechanical isolation of MOV-2516, Supervisor did not visually confirm the isolation of the breaker in electrical isolation of MOV-2516 was subsequently reversed by another employer after work on E-P3-1133 had commenced.
Recent events (3)
  • — F (O) $3000
  • — C (S) $15625
  • — Z (S) $15625

1910.147 C04 II D

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Sep 15, 2023
Abate by
Nov 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(4)(ii)(D): The employer did not implement energy control procedure with specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.  On or about May 5, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not ensure designated craft worker (Supervisor) performed specific requirements for testing the MOV-2516 to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 C06 I

Deleted Serious Gravity 10 2 instances 5 exposed
Issued
Sep 15, 2023
Abate by
Nov 2, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.   On or about May 5, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.
Recent events (3)
  • — F (S) $0
  • — C (S) $15625
  • — Z (S) $15625

1910.147 D05 II

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Sep 15, 2023
Abate by
Nov 2, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1910.147(d)(5)(ii): The verification of isolation was not continued until the servicing or maintenance was completed, or until the possibility of such accumulation no longer existed.   On or about May 5, 2023, employees were exposed to fire, explosion and toxic gas release hazards when the employer did not ensure designated craft worker (Supervisor) verified the energy isolations on MOV-2516 was continued until the servicing or maintenance on the heat exchanger E-P3-1133  was completed or until the possibility of such accumulation no longer existed.
Recent events (3)
  • — F (S) $0
  • — C (S) $15625
  • — Z (S) $15625

View UPS Industrial Services, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346693369.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.