JOINT BASE LEWIS MCCHORD, WA —
OSHA Inspection: ARMY JOINT BASE GARRISON - DIRECTORATE OF PUBLIC WORKS
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of ARMY JOINT BASE GARRISON - DIRECTORATE OF PUBLIC WORKS in 2012 LIGGETT AVE., JOINT BASE LEWIS MCCHORD, WA 98433 (NAICS 928110). OSHA activity number 346714058.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 2012 LIGGETT AVE.
- City
- JOINT BASE LEWIS MCCHORD
- State
- WA
- ZIP
- 98433
- Mailing
- BLDG 2007A N. 2ND ST MS-66 BOX 339500, JOINT BASE LEWIS MCCHORD, WA 98433
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 316
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.28 B01 I
- Issued
- Aug 7, 2023
- Abate by
- Sep 22, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(1)(i): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling: A) The catwalk system in the McChord Boiler Plant had several walkways that were open sided. Employees working on boilers from the walkways on the catwalk system with no fall protection were exposed to fall hazards of 15 to 40 foot heights.
Recent events (1)
- — Z (S) $0
1910.107 G02
- Issued
- Aug 7, 2023
- Abate by
- Sep 22, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(g)(2): Cleaning. All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary: A) In the Paint shop, there was a spray booth with accumulations of paint residue/overspray that created a rough surface over the walls of the booth. B) In the Structures shop, there was a small open-faced spray booth with accumulations of paint residue/overspray that created a rough surface over the walls and work surface of the booth.
Recent events (1)
- — Z (S) $0
1910.215 A04
- Issued
- Aug 7, 2023
- Abate by
- Sep 22, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rests. On offhand grinding machines, work rests shall be used to support the work. Work rests were not kept adjusted closely to the wheel with a maximum opening of one-eighth inch to prevent the work from being jammed between the wheel and the rest, which may cause wheel breakage: A) In the HVAC shop, there was a Promax bench grinder that had its work rest adjusted to one-quarter inch from the surface of the grinding wheel.
Recent events (1)
- — Z (S) $0
1910.215 B09
- Issued
- Aug 7, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): Exposure adjustment. Safety guards of the types described in Subparagraphs (3) and (4) of this paragraph, where the operator stands in front of the opening, shall be constructed so that the peripheral protecting member can be adjusted to the constantly decreasing diameter of the wheel. The distance between the wheel periphery and the adjustable tongue or the end of the peripheral member at the top exceeded one-fourth inch: A) In the Welding shop, there was a bench grinder where the tongue guard was not properly adjusted. The guard was seven-eighth inch from the surface of the grinding wheel.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Aug 7, 2023
- Abate by
- Sep 22, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: A) In the HVAC shop there was an energized wall mounted junction box that had several openings that were not closed.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 928110)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346714058.