Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SAN ISABEL ELECTRIC ASSOCIATION INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SAN ISABEL ELECTRIC ASSOCIATION INC in 1187 S SABINAS DR, PUEBLO WEST, CO 81007 (NAICS 221122). OSHA activity number 346754781.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch SAN Isabel Electric Association INC — free Get an email when a new federal OSHA severe-injury report for SAN Isabel Electric Association INC is published. One employer, no account, unsubscribe in one click.
Site address
1187 S SABINAS DR
City
PUEBLO WEST
State
CO
ZIP
81007
Mailing
781 EAST INDUSTRIAL BOULEVARD, PUEBLO WEST, CO 81007
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
83
Ownership type
A

4 citations on file for this inspection.

1910.269 A02 IV

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Nov 7, 2023
Abate by
Dec 5, 2023
Penalty
Initial $10,938 · Current $10,938
29 CFR  1910.269(a)(2)(iv): The employer did not determine that each employee was complying with all required safety-related work practices required by this section by regular supervision and annual inspections:  a) 1187 S Sabinas Dr, Pueblo West, CO 81007, Station #211735 Transformer: On or about June 5th, 2023 and at times prior, employees were exposed to electrical shock hazards from approaching the minimum approach distance of the exposed elbow in Station #211735 Transformer that had not been properly deenergized and/or grounded. The 200 Amp Elbow contacted the employee's bare left hand as the employee was attempting to replace the damaged elbow, resulting in an electrical shock of approximately 7200 volts. San Isabel Electric Association Inc failed to determine that each employee was complying with all required safety related work practices by not providing regular supervision during after-hours jobs.
Recent events (2)
  • — I (O) $10938
  • — Z (S) $10938

1910.269 C01 II

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Nov 7, 2023
Abate by
Dec 5, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.269(c)(1)(ii):The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job.  a) 1187 S Sabinas Dr, Pueblo West, CO 81007, Station #211735 Transformer: On or about June 5th, 2023, employees were exposed to electrical shock hazards from not conducting a Job Briefing before starting work on and around Station #211735 Transformer.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.269 M03 VII

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Nov 7, 2023
Abate by
Dec 5, 2023
Penalty
Initial $10,938 · Current $10,938
29 CFR 1910.269 (m)(3)(vii): The employer did not ensure the installation of protective grounds as required by paragraph (n) of this section.  a) 1187 S Sabinas Dr, Pueblo West, CO 81007, Station #211735 Transformer: On or about June 5th, 2023, employees were exposed to electrical shock hazards from approaching the minimum approach distance of the exposed elbow in Station #211735 Transformer that had not been properly deenergized and/or grounded. The 200 Amp Elbow contacted the employee's bare left hand as the employee was attempting to replace the damaged elbow, resulting in an electrical shock of approximately 7200 volts.
Recent events (2)
  • — I (O) $10938
  • — Z (S) $10938

1910.269 N02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Nov 7, 2023
Abate by
Dec 5, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section:  a) 1187 S Sabinas Dr, Pueblo West, CO 81007, Station #211735 Transformer: On or about June 5th, 2023, employees were exposed to electrical shock hazards from reaching into Station # 210765 to retrieve an exposed 200 Amp elbow and replace it without ensuring that the lines and equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346754781.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.