Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: US COAST GUARD BASE SAN JUAN

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of US COAST GUARD BASE SAN JUAN in 5 CALLE LA PUNTILLA, SAN JUAN, PR 00901 (NAICS 926120). OSHA activity number 346784119.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Coast Guard Base SAN Juan — free Get an email when a new federal OSHA severe-injury report for US Coast Guard Base SAN Juan is published. One employer, no account, unsubscribe in one click.
Site address
5 CALLE LA PUNTILLA
City
SAN JUAN
State
PR
ZIP
00901
Mailing
5 CALLE LA PUNTILLA, SAN JUAN, PR 00901
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926120
Employees
69
Ownership type
D

4 citations on file for this inspection.

1960.8 A

Serious Gravity 10 1 instance 5 exposed
Issued
Jul 19, 2023
Abate by
Aug 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1960.8(a): The head of each agency shall furnish to each employee employment and a place of employment which are free from recognized hazards that are causing or are likely to cause death or serious physical harm.   OSH ACT of 1970 Section (5)(a)(1):The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm inn that employees were exposed to fire hazards.  a) U.S. Coast Guard Base San Juan, West of Building 110, Near Temporary Hazardous and Universal Waste Storage Area Secondary Containment.  On or about June 22nd, 2023, a fire hydrant was obstructed by heavy chains, drums, a plastic pallet and a tow-truck trailer with a pin box in front of approximately 20  to 25 feet in length .  This action can delay Fire Department Emergency Personnel response and access to the fire hydrant and exposing employees to fire hazards considering this is the closest hydrant to the Building 110 Shops.    A feasible and acceptable methods to correct this hazardous condition would be:  1.  Clear the path of access to the fire hydrant.  2. Adhere  to and maintain 36 inches of clear space around the circumference of fire hydrants  and a clear space of not less than 60 in. (1524 mm) shall be provided in front of each hydrant connection having a diameter greater than 21?2 inches, in accordance with the Consensus Standard NFPA 1, 18.5.7.1 and 18.5.7.2, Clearance around fire hydrants.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 1 2 instances 5 exposed
Issued
Jul 19, 2023
Abate by
Aug 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1):Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) On or about June 22nd, 2023, at the US Coast Guard Base San Juan, building 110, Air Conditioning Shop, a fire extinguisher (10-pounds, dry chemical) not in its designated place, instead it was laying on a corner of the room, exposing employees to fire hazards.  b) On or about June 22nd, 2023, at the US Coast Guard Base San Juan, building 11, Hazardous Materials and Waste Storage Area, a fire extinguisher, dry-chemical, model B456 was obstructed by a large white plastic box, not allowing for easy access and exposing employees to fire hazards.  NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903 (c) and (d) respectively.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 5 exposed
Issued
Jul 19, 2023
Abate by
Aug 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a) On or about June 22nd, 2023, at the US Coast Guard Base San Juan, building 110, Air Conditioning Shop, two electrical disconnect switch panels were not readily accessible; there was a large too-box, a vacuum cleaner and other boxes in front of the switch panels area.  NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer prior to citation issuance.
Recent events (1)
  • — Z (S) $0

1910.101 B

Serious Gravity 5 2 instances 5 exposed
Issued
Jul 19, 2023
Abate by
Aug 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  a) On or about June 22nd, 2023, at Building 110, Gases Storage Area, six MAPP flammable gas cylinders were not stored in a secured area to avoid them from being struck or damaged, exposing employees to fire and explosion hazards.  b) On or about June 22nd, 2023, at Building 110, Gases Storage Area, six liquefied petroleum gas (LPG) tanks with a capacity of 15.2 pounds each, for forklifts were not secured with chains inside the cage to avoid them from falling and getting damaged, exposing employees to explosion hazards.  NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

View US Coast Guard Base SAN Juan's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346784119.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.