CULLMAN, AL —
OSHA Inspection: CORBITT POWER & LIGHT, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CORBITT POWER & LIGHT, LLC in 5351 SR 69 KNIGHTS OLD STORE, CULLMAN, AL 35057 (NAICS 221122). OSHA activity number 346843527.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CORBITT POWER & LIGHT, LLC
- Site address
- 5351 SR 69 KNIGHTS OLD STORE
- City
- CULLMAN
- State
- AL
- ZIP
- 35057
- Mailing
- 2795 ALABAMA 205, ALBERTVILLE, AL 35950
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 65
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.137 C02 XII
- Issued
- Jan 4, 2024
- Abate by
- Feb 22, 2024
- Penalty
- Initial $10,938 · Current $10,938
General-duty citation text
29 CFR 1926.97(c)(2)(xii) The employer did not certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section. (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to contact with electrical source in that, equipment, such as but not limited to, Hastings 8' External Rod Shotgun Stick Model 8108-U had not been tested and certified for the worksite where employees were performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary. In the alternative 29 CFR 1910.137(c)(2)(xii): The employer did not certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section: (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, equipment, such as but not limited to, Hastings 8' External Rod Shotgun Stick Model 8108-U had not been tested and certified for the worksite where employees were performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary.
Recent events (1)
- — Z (S) $10938
1926.97 C02 VIII
- Issued
- Jan 4, 2024
- Abate by
- Feb 22, 2024
- Penalty
- Initial $9,376 · Current $9,376
General-duty citation text
29 CFR 1926.97(c)(2)(viii):Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5: (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, the rubber gloves used by employees performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary had not been tested as required.
Recent events (1)
- — Z (S) $9376
1926.959 D02
- Issued
- Jan 4, 2024
- Abate by
- Feb 22, 2024
- Penalty
- Initial $10,938 · Current $10,938
General-duty citation text
29 CFR 1926.959(d)(2):A designated employee other than the equipment operator did not observe the approach distance to exposed lines and equipment and provide timely warnings such that the minimum approach distance was being maintained before the minimum approach distance required by paragraph (d)(1) of this section was reached: (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, a designated observer did not warn employees performing tasks in close proximity to three phase, 14400 V energized primary, such as but not limited to, connecting underground secondary to a vertical pole mounted switch.
Recent events (1)
- — Z (S) $10938
More inspections in this industry (NAICS 221122)
More inspections in AL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346843527.