Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CORBITT POWER & LIGHT, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CORBITT POWER & LIGHT, LLC in 5351 SR 69 KNIGHTS OLD STORE, CULLMAN, AL 35057 (NAICS 221122). OSHA activity number 346843527.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Corbitt Power & Light, LLC — free Get an email when a new federal OSHA severe-injury report for Corbitt Power & Light, LLC is published. One employer, no account, unsubscribe in one click.
Site address
5351 SR 69 KNIGHTS OLD STORE
City
CULLMAN
State
AL
ZIP
35057
Mailing
2795 ALABAMA 205, ALBERTVILLE, AL 35950
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
65
Ownership type
A

3 citations on file for this inspection.

1910.137 C02 XII

Serious Gravity 10 1 instance 7 exposed
Issued
Jan 4, 2024
Abate by
Feb 22, 2024
Penalty
Initial $10,938 · Current $10,938
29 CFR 1926.97(c)(2)(xii) The employer did not certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section.   (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to contact with electrical source in that, equipment, such as but not limited to, Hastings 8' External Rod Shotgun Stick Model 8108-U had not been tested and certified for the worksite where employees were performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary.  In the alternative  29 CFR 1910.137(c)(2)(xii): The employer did not certify that equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section:   (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, equipment, such as but not limited to, Hastings 8' External Rod Shotgun Stick Model 8108-U had not been tested and certified for the worksite where employees were performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary.
Recent events (1)
  • — Z (S) $10938

1926.97 C02 VIII

Serious Gravity 5 1 instance 7 exposed
Issued
Jan 4, 2024
Abate by
Feb 22, 2024
Penalty
Initial $9,376 · Current $9,376
29 CFR  1926.97(c)(2)(viii):Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5:  (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, the rubber gloves used by employees performing tasks, such as but not limited to, connecting underground secondary to a vertical pole mounted switch near three phase 14,400 V energized primary had not been tested as required.
Recent events (1)
  • — Z (S) $9376

1926.959 D02

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 4, 2024
Abate by
Feb 22, 2024
Penalty
Initial $10,938 · Current $10,938
29 CFR  1926.959(d)(2):A designated employee other than the equipment operator did not observe the approach distance to exposed lines and equipment and provide timely warnings such that the minimum approach distance was being maintained before the minimum approach distance required by paragraph (d)(1) of this section was reached:  (a) At 5351 SR 69, Cullman, AL: On or about 7/12/2023, the employer exposed employees to electrical hazards in that, a designated observer did not warn employees performing tasks in close proximity to three phase, 14400 V energized primary, such as but not limited to, connecting underground secondary to a vertical pole mounted switch.
Recent events (1)
  • — Z (S) $10938

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346843527.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.