Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GRAY MATTER HOLDINGS INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GRAY MATTER HOLDINGS INC. in 1999 POLAND AVE, YOUNGSTOWN, OH 44502 (NAICS 518210). OSHA activity number 346855315.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gray Matter Holdings INC. — free Get an email when a new federal OSHA severe-injury report for Gray Matter Holdings INC. is published. One employer, no account, unsubscribe in one click.
Site address
1999 POLAND AVE
City
YOUNGSTOWN
State
OH
ZIP
44502
Mailing
ATTN: ANTHONY DAVIAN 9733 YORK BETA DRIVE NORTH, NORTH ROYALTON, OH 44133
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
518210
Employees
8
Ownership type
A

5 citations on file for this inspection.

1910.157 C01

Serious Gravity 1 1 instance 7 exposed
Issued
Oct 27, 2023
Abate by
Dec 15, 2023
Penalty
Initial $2,678 · Current $2,678
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) On or about July 25, 2023, technicians maintaining "Asic miners" in the mine are exposed to fire hazards due to arc flashes within the electrical systems of the PDU's (power distribution units) and PSU's (power supply units); the employer did not ensure the portable fire extinguishers were mounted and identified to be readily accessible within the mine.
Recent events (1)
  • — Z (S) $2678

1910.157 G01

Serious Gravity 1 1 instance 7 exposed
Issued
Oct 27, 2023
Abate by
Dec 15, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(g)(1):An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:  a) On or about July 25, 2023, where technicians maintaining "Asic miners" in the mine are exposed to fire hazards due to arc flashes within the electrical systems of the PDU's (power distribution units) and PSU's (power supply units) and are expected to utilizer fire extinguishers in the event of a fire; the employer did not ensure an educational program was provided for all employees to familiarize them with portable fire extinguishers.
Recent events (1)
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 7 exposed
Issued
Oct 27, 2023
Abate by
Dec 15, 2023
Penalty
Initial $3,572 · Current $3,572
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment:  a) On or about July 25, 2023, technicians working on the "data miners" in the mine were exposed to 415-volt electrical shock and ARC flash hazards while disconnecting the "data miners" from the PDU's for maintenance; the employer did not ensure all unused openings on the 415-volt PDU's were effectively closed to afford protection equivalent to the wall of the equipment.
Recent events (1)
  • — Z (S) $3572

1910.303 H02 III A

Serious Gravity 5 1 instance 7 exposed
Issued
Oct 27, 2023
Abate by
Dec 15, 2023
Penalty
Initial $4,465 · Current $4,465
29 CFR 1910.303(h)(2)(iii)(A): The installations shall be made with metal-enclosed equipment or shall be enclosed in a vault or in an area to which access is controlled by a lock;  a) On or about July 25, 2023, technicians inspecting the mine were exposed to electrical shock and arc flash hazards due to the vaults not being controlled by a lock; the employer did not ensure the vault were locked to other than qualified persons exposing technicians to electrical shock and arc flash hazards.
Recent events (1)
  • — Z (S) $4465

1910.335 A01 I

Serious Gravity 5 1 instance 7 exposed
Issued
Oct 27, 2023
Abate by
Dec 15, 2023
Penalty
Initial $4,465 · Current $4,465
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  a) On or about July 14, 2023, technicians energizing/de-energizing the 12,470-volt main switchgear using the load interrupter switch or resetting the breaker panel were exposed to an electrical shock and arc flash hazard to their face and body; the employer did not ensure the use of electrical protective equipment for technicians face and body while energizing/de-energizing the 12.470-volt main switchgear and resetting the breaker panel.
Recent events (1)
  • — Z (S) $4465

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346855315.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.