OSHA Inspection: NATIONAL PARK SERVICE NORTH CASCADES, ROSS LAKE DAM BOATHOUSE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE NORTH CASCADES, ROSS LAKE DAM BOATHOUSE in ROSS LAKE DAM, MARBLEMOUNT, WA 98267 (NAICS 712190). OSHA activity number 346862022.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service North Cascades, Ross Lake DAM Boathouse — free Get an email when a new federal OSHA severe-injury report for National Park Service North Cascades, Ross Lake DAM Boathouse is published. One employer, no account, unsubscribe in one click.
Site address
ROSS LAKE DAM
City
MARBLEMOUNT
State
WA
ZIP
98267
Mailing
810 STATE ROUTE 20, SEDRO WOOLLEY, WA 98284
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
69
Ownership type
D

6 citations on file for this inspection.

1910.157 C01

Serious Gravity 1 1 instance 26 exposed
Issued
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) Boathouse Shop, where the Badger fire extinguisher was blocked by items including a spool of rope, a trash can, and a cart containing an oxygen and acetylene cylinder.
Recent events (1)
  • — Z (S) $0

1910.184 D

Serious Gravity 5 1 instance 26 exposed
Issued
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.184(d): Damaged or defective sling(s) were not immediately removed from service:  a) Boathouse Shop, where synthetic slings equipped with snags and cuts were not removed from service.
Recent events (1)
  • — Z (S) $0

1910.157 E02

Repeat Gravity 1 3 instances 26 exposed
Issued
Sep 18, 2023
Abate by
Nov 3, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a) Boathouse, where employees would be expected to fight incipient stage fires, fire extinguishers not inspected on a monthly basis included:  1. Boathouse Shop, where the tag on the Badger fire extinguisher indicated the last monthly inspection had been done September 10, 2021.  2. Boathouse Housing, where the tag on the Ansul Sentry fire extinguisher indicated the last monthly inspection had been done September 10, 2021.  3. Boathouse, where the tag on the Kidde fire extinguisher indicated the last monthly inspection had been done September 10, 2021.  The National Park Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(2), which was contained in OSHA inspection number 1450538, citation no. 1, item no. 1b, and was affirmed as a final order on February 4, 2020, with respect to a workplace at Seattle, WA.
Recent events (1)
  • — Z (R) $0

1910.157 E03

Repeat Gravity 1 3 instances 26 exposed
Issued
Sep 18, 2023
Abate by
Nov 3, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  a) Boathouse, where employees would be expected to fight incipient stage fires, fire extinguishers not inspected annually included:  1. Boathouse Shop, where the tag on the Badger fire extinguisher indicated the last annual inspection had been done September 10, 2021.  2. Boathouse Housing, where the tag on the Ansul Sentry fire extinguisher indicated the last annual inspection had been done in August 2016.  3. Boathouse, where the tag on the Kidde fire extinguisher indicated the last monthly inspection had been done September 10, 2021.  The National Park Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(e)(3), which was contained in OSHA inspection number 1450538, citation no. 1, item no. 1c, and was affirmed as a final order on February 4, 2020, with respect to a workplace at Seattle, WA.
Recent events (1)
  • — Z (R) $0

1910.253 B04 III

Repeat Gravity 1 1 instance 26 exposed
Issued
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  a) Boathouse Shop, where one oxygen and one acetylene cylinder were stored together on a cart.  The National Park Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.253(b)(4)(iii), which was contained in OSHA inspection number 1607695, citation no. 1, item no. 2, and was affirmed as a final order on September 9, 2022, with respect to a workplace at Walla Walla, WA.
Recent events (1)
  • — Z (R) $0

1910.305 J02 VII

Repeat Gravity 1 2 instances 26 exposed
Issued
Sep 18, 2023
Abate by
Nov 3, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.305(j)(2)(vii): A receptacle installed in a wet location where the product intended to be plugged into it was to be attended while in use (for example, portable tools) did not have an enclosure that was weatherproof when the attachment plug cap was removed:   a) Boathouse, where weatherproof receptacles located outdoors and not equipped with covers included:  1. The receptacle located on the exterior of the building adjacent to the personnel door.  2. The receptacle located on the Ross Mule landing craft.  The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(j)(2)(vii), which was contained in OSHA inspection number 1605139, citation no. 1, item no. 3, and was affirmed as a final order on October 12, 2022, with respect to a workplace at Marblemount, WA.