WILMINGTON, DE —
OSHA Inspection: PEPSICO SALES, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PEPSICO SALES, INC. in 3501 GOVERNOR PRINTZ BOULEVARD, WILMINGTON, DE 19802 (NAICS 312111). OSHA activity number 346877186.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PEPSICO SALES, INC.
- Site address
- 3501 GOVERNOR PRINTZ BOULEVARD
- City
- WILMINGTON
- State
- DE
- ZIP
- 19802
- Mailing
- 3501 GOVERNOR PRINTZ BOULEVARD, WILMINGTON, DE 19802
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 312111
- Employees
- 250
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.37 A03
- Issued
- Sep 29, 2023
- Penalty
- Initial $8,036 · Current $5,625 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) 3501 Governor Printz Blvd (Lower Warehouse): On or about August 3, 2023, and at times prior thereto, impediments to the exit routes, created by items such as but not limited to pallets and equipment which blocked the exit paths, were not minimized exposing employees to trip hazards and a delayed egress in the event of an emergency.
Recent events (2)
- — I (S) $5625.2
- — Z (S) $8036
1910.37 A04
- Issued
- Sep 29, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) 3501 Governor Printz Blvd (Lower Warehouse): On or about August 3, 2023, employees were exposed to hazards related to emergency evacuation of the building while working in the area where the emergency lighting leading to the exit access was not illuminated to ensure visibility in the event of an emergency evacuation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 B02
- Issued
- Sep 29, 2023
- Penalty
- Initial $6,026 · Current $4,218 Reduced
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) 3501 Governor Printz Blvd (Exit door under Canopy): On or about August 3, 2023, and at times prior thereto, the employer exposed employees to exit egress routes and exits that were not clearly visible or marked as an exit.
Recent events (2)
- — I (S) $4218.2
- — Z (S) $6026
1910.37 B04
- Issued
- Sep 29, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) 3501 Governor Printz Blvd (Lower Warehouse): On or about August 3, 2023, the employer failed to provide directional signs along the exit access to provide direction of travel to the nearest exit and exit discharge.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B01 VII
- Issued
- Sep 29, 2023
- Penalty
- Initial $8,036 · Current $5,625 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(vii): Electric equipment was not free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment was not determined by classification by type, size, voltage, current capacity, and specific use: a) 3501 Governor Printz Blvd (Lower Warehouse): On or about August 3, 2023, and days prior, employees were exposed to 277/480 V electrical equipment that was not properly marked with a classification, size, voltage, current capacity, or arc flash rating.
Recent events (2)
- — I (S) $5625.2
- — Z (S) $8036
More inspections at Pepsico Sales, INC.
View Pepsico Sales, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 312111)
More inspections in DE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346877186.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.