OSHA Inspection: STS INDUSTRIAL INCORPORATED

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of STS INDUSTRIAL INCORPORATED in 2917E EAST ROUNDBUNCH ROAD, ORANGE, TX 77630 (NAICS 423710). OSHA activity number 346909898.

Watch STS Industrial Incorporated — free Get an email when a new federal OSHA severe-injury report for STS Industrial Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
2917E EAST ROUNDBUNCH ROAD
City
ORANGE
State
TX
ZIP
77630
Mailing
3067 CARBIDE DR., SULPHUR, LA 70665
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423710
Employees
20
Ownership type
A

10 citations on file for this inspection.

1910.28 B11 II

Serious Gravity 5 1 instance 10 exposed
Issued
Penalty
Initial $6453.00 · Current $3871.00 Reduced
29 CFR 1910.28(b)(11)(ii): The employer did not ensure that each flight of stairs having at least 3 treads and at least 4 risers was equipped with stair rail systems and handrails as described in 29 CFR 1910.28 Table D-2, Stairway Handrail Requirements.  a) Stairway leading to upstairs office area was not equipped with a stair rails system with handrails on the open side.
Recent events (2)
  • — I (S) $3871
  • — Z (S) $6453

1910.147 C01

Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $11292.00 · Current $6775.00 Reduced
29 CFR  1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training, and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  a) Procedures for the control of energy when employees performed blade changes on equipment such as SYO-MECH, S-20A Series II, band saw had not been established.
Recent events (2)
  • — I (S) $6775
  • — Z (S) $11292

1910.147 C04 I

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $11292.00 · Current $0.00 Reduced
29 CFR  1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  a) On or about August 15, 2023, on the facility floor, procedures had not been developed, documented and utilized for the control of potentially hazardous energy when employees performed blade changes on equipment such as the HYD-MECH, S-20A Series II band saw.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11292

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $8067.00 · Current $4840.00 Reduced
29 CFR  1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a) HYD-MECH, S-20A Series II, band saw missing guard for rotating blade.
Recent events (2)
  • — I (S) $4840
  • — Z (S) $8067

1910.303 F02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $8067.00 · Current $4840.00 Reduced
29 CFR  1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Unused openings in electrical panel were not sufficiently labeled as unused.
Recent events (2)
  • — I (S) $4840
  • — Z (S) $8067

1910.305 B01 II

Serious Gravity 10 2 instances 4 exposed
Issued
Penalty
Initial $11292.00 · Current $0.00 Reduced
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) An unused opening in the junction box and unused openings on the electrical panel were not effectively closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11292

1910.305 B02 I

Serious Gravity 10 2 instances 3 exposed
Issued
Penalty
Initial $11292.00 · Current $0.00 Reduced
29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.  In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy:  a) Junction box on wall was not effectively covered.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11292

1910.303 G02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $11292.00 · Current $8469.00 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a) On or about August 14, 2023, where a receptable on wall with guard not in place.
Recent events (2)
  • — I (S) $8469
  • — Z (S) $11292

1910.304 G05

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $11292.00 · Current $8469.00 Reduced
29 CFR  1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a) On or about August 14, 2023, on the facility floor,  electrical equipment was plugged into an extension cord with a missing ground prong.
Recent events (2)
  • — I (S) $8469
  • — Z (S) $11292

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $11292.00 · Current $8469.00 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:  a) On or about August 14, 2023, energy control procedures were not utilized to de-energize electrical circuits prior to maintenance.