Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TAYSE INTERNATIONAL TRADING, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TAYSE INTERNATIONAL TRADING, INC. in 501 RICHARDSON RD SE, CALHOUN, GA 30701 (NAICS 314110). OSHA activity number 346910938.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tayse International Trading, INC. — free Get an email when a new federal OSHA severe-injury report for Tayse International Trading, INC. is published. One employer, no account, unsubscribe in one click.
Site address
501 RICHARDSON RD SE
City
CALHOUN
State
GA
ZIP
30701
Mailing
501 RICHARDSON RD SE, CALHOUN, GA 30701
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
314110
Employees
45
Ownership type
A

4 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 20, 2023
Abate by
Jan 22, 2024
Penalty
Initial $12,031 · Current $6,016 Reduced
29 CFR 1910.332(b)(1):  Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a) Throughout Facility: On or about June 21, 2023, and at times prior, the employer exposed employees to electrical hazards, in that training in electrical safe work practices was not provided to employees required to install, service or maintain electrical equipment energized to 480 volts.
Recent events (2)
  • — I (S) $6015.5
  • — Z (S) $12031

1910.332 B03 I

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 20, 2023
Abate by
Jan 22, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(3)(i): Qualified persons (i.e., those permitted to work on or near exposed energized parts) were not, at a minimum, trained in and familiar with the skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment.  a) Throughout Facility: On or about June 21, 2023, and at times prior, the employer exposed employees to electrical hazards, in that training in safe work practices for distinguishing exposed live parts from other parts of electric equipment was not provided for employees required to install, service or maintain electrical equipment energized to 480 volts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 II B

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 20, 2023
Abate by
Dec 29, 2023
Penalty
Initial $12,031 · Current $6,016 Reduced
29 CFR  1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources.   a) Electrical Room, distribution panel 8: On or about June 21, 2023, and times prior the employer exposed employees to electrical hazards, in that an electrical disconnect was not deenergized and locked out before the cover panel of the disconnect was removed by an employee tasked to install a 480 electrical line to provide power to a forklift battery charging unit.
Recent events (2)
  • — I (S) $6015.5
  • — Z (S) $12031

1910.132 D02

Other-than-serious 1 instance 1 exposed
Issued
Dec 20, 2023
Abate by
Jan 5, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2).  a)	Distribution Panel 8 Electrical Room: On or about June 21, 2023, and times prior the employer exposed employees to electrical hazards, in that the employer did not certify the completion of a hazard assessment to identify exposures which would necessitate the use of personal protective equipment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Tayse International Trading, INC.'s full OSHA safety record →