APPLETON, WI —
OSHA Inspection: PLUG LIGHT BULB ELECTRICAL SERVICES LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PLUG LIGHT BULB ELECTRICAL SERVICES LLC in 110 NORTH FOX RIVER DR, APPLETON, WI 54913 (NAICS 238210). OSHA activity number 346911514.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PLUG LIGHT BULB ELECTRICAL SERVICES LLC
- Site address
- 110 NORTH FOX RIVER DR
- City
- APPLETON
- State
- WI
- ZIP
- 54913
- Mailing
- 3377 PACKERLAND DRIVE, DE PERE, WI 54115
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 20
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.20 B02
- Issued
- Dec 14, 2023
- Penalty
- Initial $6,250 · Current $4,375 Reduced
General-duty citation text
29 CFR 1926.20(b)(2): Accident prevention responsibilities. It shall be the responsibility of the employer to initiate and maintain such programs as may be necessary to comply with this part; such programs shall provide for frequent and regular inspections of the job sites, materials, and equipment to be made by competent persons designated by the employers. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, the employer did not ensure that a competent person had conducted frequent and regular inspections to correct recognizable hazards associated with the installation and use of electrical equipment. No covers were installed on energized panelboards with exposed wires, no plate installed on light switch box, and panelboard disconnects were not identified with labels.
Recent events (2)
- — I (S) $4375
- — Z (S) $6250
1926.403 H
- Issued
- Dec 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h): Electrical Identification of disconnecting means and circuits. Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. These markings shall be of sufficient durability to withstand the environment involved. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, employees were exposed to potential electrical hazards while installing and using electrical equipment without the main electric panelboard disconnect switches identified with labels. Using panelboards to power the building and to power building lighting during installation of lighting wires on a panelboard and receptable outlets.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 D
- Issued
- Dec 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(d): Switchboards and panelboards. Switchboards that have any exposed live parts shall be located in permanently dry locations and accessible only to qualified persons. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons. Exposed blades of knife switches shall be dead when open. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, employees were exposed to electrical hazards walking and working in the Electrical Room with exposed live parts in three panel boxes without dead fronts or covers installed. An employee was working in a panel box within three feet of two panel boxes, employee was turning off and on circuit switches in the panel boxes, and employees were walking and working in the Electrical room as a path to the Equipment room, to use wall light switches, and to use a ladder to access an overhead work area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 J01 I
- Issued
- Dec 14, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(j)(1)(i): Live parts. Fixtures, lampholders, lamps, rosettes, and receptacles shall have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 8 feet (2.44 m) above the floor may have exposed parts. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, employees were exposed to electrical hazards using wall light switches without the wall plates installed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.417 A
- Issued
- Dec 14, 2023
- Abate by
- Jan 16, 2024
- Penalty
- Initial $6,250 · Current $0 Reduced
General-duty citation text
29 CFR 1926.417(a): Lockout and tagging of circuits. Controls. Controls that are to be deactivated during the course of work on energized or deenergized equipment or circuits shall be tagged. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, employees were exposed to potential electrical hazards while installing lighting equipment without tagging the de-energized circuit controls. An employee was de-energizing circuits in the Main, Panel A, and Panel B boxes when terminating wires on the panelboards and installing lighting equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $6250
1926.417 B
- Issued
- Dec 14, 2023
- Abate by
- Jan 16, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.417(b): Lockout and tagging of circuits. Equipment and circuits. Equipment or circuits that are deenergized shall be rendered inoperative and shall have tags attached at all points where such equipment or circuits can be energized. On or about August 15, 2023, at 110 North Fox River Drive in Appleton, Wisconsin, employees were exposed to potential electrical hazards while installing lighting equipment without rendering the de-energized circuits inoperative. An employee was turning off circuit switches in the Main, Panel A, and Panel B boxes when terminating wires on the panelboards and installing lighting equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Plug Light Bulb Electrical Services LLC
View Plug Light Bulb Electrical Services LLC's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346911514.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.