SAN JUAN, PR —
OSHA Inspection: SAN JUAN INTERIORS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SAN JUAN INTERIORS in 10 CASIA ST, SAN JUAN, PR 00917 (NAICS 337110). OSHA activity number 346938897.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SAN JUAN INTERIORS
- Site address
- 10 CASIA ST
- City
- SAN JUAN
- State
- PR
- ZIP
- 00917
- Mailing
- PO BOX 6496, SAN JUAN, PR 00914
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337110
- Employees
- 2
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.34 A
- Issued
- Jan 9, 2024
- Penalty
- Initial $2,009 · Current $2,009
General-duty citation text
29 CFR 1926.34(a): Building or structure exits were not so arranged and maintained as to provide free and unobstructed egress from all parts of the building or structure at all times when it was occupied: (a) On or about 8/18/2023, 10 Casia St, San Juan, PR, Emergency Room Addition - exits were not readily accessible, exposing employees to a fire hazard. NOTE: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
- — Z (S) $2009
1926.403 B01
- Issued
- Jan 9, 2024
- Penalty
- Initial $4,688 · Current $4,688
General-duty citation text
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees: (a) On or about 8/18/2023, 10 Casia St, San Juan, PR, Emergency Room Addition Bathroom - the extension cord used to power multiple electrical equipment was being used while conductors were exposed on the female end of the extension cord, exposing employees to electrical hazard. NOTE: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
- — Z (S) $4688
1926.405 B02
- Issued
- Jan 9, 2024
- Penalty
- Initial $2,679 · Current $2,679
General-duty citation text
29 CFR 1926.405(b)(2): In an energized installation, each outlet box did not have a cover, faceplate, or fixture canopy. (a) On or about 8/18/2023, 10 Casia St, San Juan, PR, Emergency Room Counter Area - (1) Electrical Box (2" x 4") was not covered or closed, exposing employees to an electrical hazard. NOTE: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
- — Z (S) $2679
1926.405 D
- Issued
- Jan 9, 2024
- Penalty
- Initial $2,679 · Current $2,679
General-duty citation text
29 CFR 1926.405(d): Switchboards having exposed live parts were not located in permanently dry locations and accessible only to qualified persons: (a) On or about 8/18/2023, 10 Casia St, San Juan, PR, Emergency Room Addition Electrical room - access to three energized panels, with front panels removed, was provided to unauthorized and unqualified personnel, exposing employees to electrical hazards. NOTE: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
- — Z (S) $2679
More inspections in this industry (NAICS 337110)
More inspections in PR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346938897.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.