Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ROYALE PIGMENTS AND CHEMICALS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ROYALE PIGMENTS AND CHEMICALS, INC. in 400 CARSON DRIVE, BEAR, DE 19701 (NAICS 325320). OSHA activity number 346953995.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Royale Pigments and Chemicals, INC. — free Get an email when a new federal OSHA severe-injury report for Royale Pigments and Chemicals, INC. is published. One employer, no account, unsubscribe in one click.
Site address
400 CARSON DRIVE
City
BEAR
State
DE
ZIP
19701
Mailing
400 CARSON DRIVE, BEAR, DE 19701
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325320
Employees
26
Ownership type
A

5 citations on file for this inspection.

1910.106 B06

Serious Gravity 5 1 instance 6 exposed
Issued
Feb 23, 2024
Penalty
Initial $6,050 · Current $4,235 Reduced
29 CFR 1910.106(b)(6): Sources of ignition were not eliminated or controlled where the presence of flammable vapors was possible:   a) 400 Carson Drive, Bear, DE 19701: On or about August 29, 2023, employees were exposed to category-2 flammable vapors when a tanker trailer was leaking in the unloading area within the back side of the building where it was parking without any ignition source being eliminated
Recent events (2)
  • — I (S) $4235
  • — Z (S) $6050

1910.106 D07 I

Serious Gravity 5 1 instance 6 exposed
Issued
Feb 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(7)(i): Suitable fire control devices, such as small hose or portable fire extinguishers, were not available at locations where flammable liquids were stored:  a) 400 Carson Drive, Bear, DE 19701: On or about August 29, 2023, flammable liquids were stored in an area where fire control devices were not made readily available to employees in the event of a fire and a need to egress from the area. The chemical storage area contained no less than 24 barrels of flammable liquids that were considered highly flammable liquid and vapor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E09 I

Serious Gravity 5 1 instance 6 exposed
Issued
Feb 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(9)(i): Spills of flammable liquids were not cleaned up promptly:  a) 400 Carson Drive, Bear, DE 19701: On or about August 29, 2023, a class 2 flammable liquid was leaking from a trailer and not cleaned up promptly to remove the vapors and/or liquid from being exposed to ignition sources creating an explosive atmosphere.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 B05

Serious Gravity 5 1 instance 6 exposed
Issued
Feb 23, 2024
Penalty
Initial $7,260 · Current $5,082 Reduced
29 CFR 1910.304(b)(5): A receptacle outlet shall be installed wherever flexible cords with attachment plugs are used.  a) 400 Carson Drive, Bear, DE 19701: On or about August 29, 2023, employer used a flexible cord to continually power a company's air compressor exposing employees to electrical burns and/or shock hazards.
Recent events (2)
  • — I (S) $5082
  • — Z (S) $7260

1910.305 E01

Serious Gravity 5 1 instance 6 exposed
Issued
Feb 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a) 400 Carson Drive, Bear, DE 19701: On or about August 29, 2023, employees mixing chemicals or accessing emergency showers were exposed to electrical components that were not designed to prevent water from entering them.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346953995.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.