SAUGET, IL —
OSHA Inspection: CAPITAL ELECTRIC CONSTRUCTION DBA BELL ELECTRICAL CONTRACTORS
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of CAPITAL ELECTRIC CONSTRUCTION DBA BELL ELECTRICAL CONTRACTORS in 231 MONSANTO AVENUE, SAUGET, IL 62201 (NAICS 238210). OSHA activity number 346960024.
Where did this inspection happen?
- Site address
- 231 MONSANTO AVENUE
- City
- SAUGET
- State
- IL
- ZIP
- 62201
- Mailing
- 1311 NORTH HIGHWAY DRIVE, FENTON, MO 63099
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 162
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.333 B02 II A
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(A): Safe procedures for deenergizing circuits and equipment were not determined before circuits or equipment are deenergized. On or about August 14, 2023, safe procedures for deenergizing all electrical energy sources located in the outdoor tank farm metal raceway were not determined prior to employees working to replace/reinstall the conductors. The Active Group Lockout #30 "Tank Farm" procedures did not identify and address the 'Truck Loadout Pump' circuit, energized through circuit breaker #17 in the MSP-3 panel located in the DDE MCC room.
Recent events (3)
- — F (S) $0
- — C (S) $16131
- — Z (S) $16131
1910.333 B02 IV B
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized: On or about August 14, 2023, a qualified person did not use test equipment to test and verify a 480-volt conductor for the 'Truck Loadout Pump' circuit, energized through circuit breaker #17 in the MSP-3 panel located in the DDE MCC room was deenergized prior to work started to replace wiring in the outdoor raceway.
Recent events (3)
- — F (S) $0
- — C (S) $14518
- — Z (S) $14518
1910.335 A01 I
- Issued
- Abate by
- Penalty
- Initial $14518.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about August 14, 2023, employees working to repair/replace electrical wiring in an outdoor electrical raceway containing 480-volt conductors to various electrical circuits, did not utilize electrical protective equipment such as, but not limited to, gloves.
Recent events (3)
- — F (S) $0
- — C (S) $14518
- — Z (S) $14518
1904.39 A02
- Issued
- Abate by
- Penalty
- Initial $10372.00 · Current $10372.00
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in the in-patient hospitalization, amputation or the loss of an eye. On or about August 14, 2023, the employer did not report within 24-hours a work-related incident resulting in an in-patient hospitalization.
Recent events (3)
- — F (O) $10372
- — C (O) $10372
- — Z (O) $10372
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in IL
DEERFIELD, IL—2026-07-16
JOHN BURNS CONSTRUCTION COMPANY, LLC
BANNOCKBURN, IL—2026-07-16
BUILDER SERVICES GROUP, INC. DBA CJ INSULATION
BANNOCKBURN, IL—2026-07-16
ROOFING H.P. LLC
HIGHLAND PARK, IL—2026-07-16
UNITED PLUMBING AND DRAIN, INC.
FRANKLIN PARK, IL—2026-07-16
B & M PLASTIC INC.
Source