Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CROSSROADS BUILDING SUPPLY, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CROSSROADS BUILDING SUPPLY, INC. in 104 DAVIS, HOT SPRINGS, AR 71901 (NAICS 423330). OSHA activity number 347037558.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Crossroads Building Supply, INC. — free Get an email when a new federal OSHA severe-injury report for Crossroads Building Supply, INC. is published. One employer, no account, unsubscribe in one click.
Site address
104 DAVIS
City
HOT SPRINGS
State
AR
ZIP
71901
Mailing
104 DAVIS DR, HOT SPRINGS, AR 71901
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423330
Employees
5
Ownership type
A

6 citations on file for this inspection.

1910.138 A

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 12, 2024
Abate by
May 8, 2024
Penalty
Initial $10,372 · Current $7,260 Reduced
29 CFR 1910.138(a): The employer did not select and require employee(s) to use appropriate hand protection when employees' hands were exposed to hazards such as those from skin absorption of harmful substances; severe cuts or lacerations; severe abrasion:   On or about October 16, 2023, in the gutter department, employees were handling material such as, but not limited to gutter rolls without adequate hand protection.
Recent events (2)
  • — I (S) $7260.4
  • — Z (S) $10372

1910.303 B02

Serious Gravity 5 4 instances 3 exposed
Issued
Apr 12, 2024
Abate by
May 24, 2024
Penalty
Initial $12,445 · Current $8,712 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about October 16, 2023, in the warehouse, employees were engaged in activities such as, but not limited to filling orders for siding and gutters where Romex was used to provide power to electrical equipment throughout the facility and not concealed behind walls.
Recent events (2)
  • — I (S) $8711.5
  • — Z (S) $12445

1910.303 B07

Serious Gravity 5 4 instances 3 exposed
Issued
Apr 12, 2024
Abate by
May 24, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7):  Electrical equipment was not installed in a neat and workmanlike manner:   On or about October 16, 2023, in the warehouse, employees were engaged in activities such as, but not limited to filling orders for siding and gutters where: a) Electrical connections were not made in approved boxes; b) Electrical splices were not made in approved boxes; c) Motion sensor light switch installed outside of the electrical box; d) Live ends of electrical wires were not capped.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 12, 2024
Abate by
May 24, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):   On or about October 17, 2023, in the lower warehouse, employees were engaged in activities such as, but not limited to filling orders for siding and gutters where bare wire was hanging approximately 6.5 feet high from the floor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 12, 2024
Abate by
May 8, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   On or about October 16, 2023, in the warehouse, a metal 2-gang toggle switch cover was used on a box containing only a single toggle switch.  The unused opening was not filled and the cover was not effectively closed due to a motion-sensing switch being installed outside of the box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 12, 2024
Abate by
May 24, 2024
Penalty
Initial $6,222 · Current $4,355 Reduced
29 CFR  1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:   On or about October 17, 2023, in the warehouse, employees were engaged in activities such as, but not limited to filling orders for siding and gutters where the Romex 12/2 with ground wiring that supplied power to the outlets, switches and lights was not grounded.
Recent events (2)
  • — I (S) $4355.4
  • — Z (S) $6222

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347037558.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.