Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: APAHOUSER INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of APAHOUSER INC in 40 HAYES MEMORIAL DRIVE, MARLBOROUGH, MA 01752 (NAICS 332710). OSHA activity number 347063000.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Apahouser INC — free Get an email when a new federal OSHA severe-injury report for Apahouser INC is published. One employer, no account, unsubscribe in one click.
Establishment
APAHOUSER INC
Site address
40 HAYES MEMORIAL DRIVE
City
MARLBOROUGH
State
MA
ZIP
01752
Mailing
40 HAYES MEMORIAL DR, MARLBOROUGH, MA 01752
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
30
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 5 exposed
Issued
Feb 26, 2024
Abate by
Apr 11, 2024
Penalty
Initial $4,839 · Current $3,387 Reduced
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.   Location: In various locations throughout workshop areas.  a) On or about 10/26/2023,employees were exposed to fire and electric shock from the improper use of extension cords and power strips. Several extension cords were visible daisy-chained and coiled around permanent wire conduits above work benches in the assembly area of the workshop.   b) On or about 10/26/2023, employees were exposed to fire and electric shock from the improper use of extension cords and power strips. A retractable extension cord was daisy chained to another retractable extension cord which was connected to a main branch circuit hanging down in the silk screening area of the workshop.
Recent events (2)
  • — I (S) $3387.3
  • — Z (S) $4839

1910.303 G01 I B

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 26, 2024
Abate by
Apr 11, 2024
Penalty
Initial $6,453 · Current $4,517 Reduced
29 CFR  1910.303(g)(1)(i)(B):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater.   Location: Workshop wall adjacent to the quality assurance office.  On or about 10/26/2023, circuit breaker panels in the workshop were found to be inaccessible because equipment and boxes were stored in such a way that they obstructed the required minimum of 30 inches of working space in front of the panel.
Recent events (2)
  • — I (S) $4517.1
  • — Z (S) $6453

1910.303 G01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 26, 2024
Abate by
Apr 11, 2024
Penalty
Initial $11,292 · Current $7,904 Reduced
29 CFR  1910.303(g)(1)(ii): The required working space about electrical equipment rated 600 volts, nominal, or less to ground, was in a passageway or general open space and was not suitably guarded when normally enclosed live parts were exposed for inspection or servicing.  Location: Metal workshop area perimeter wall  On or about 10/26/2023, employees were at risk of electrocution due to a flexible conduit with live exposed wires being wedged between the wall and solid wire conduit within two feet of a passageway.
Recent events (2)
  • — I (S) $7904.4
  • — Z (S) $11292

1910.305 B02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 26, 2024
Abate by
Apr 11, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i):Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  Location: Metal workshop area perimeter wall   On or about 10/26/2023, employees were at risk of electrocution due to an energized outlet box that was missing its cover. This box was mounted to the exterior wall inside the metal workshop area easily accessible from the area passageway.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 C04

Other-than-serious 2 instances 5 exposed
Issued
Feb 26, 2024
Abate by
Apr 11, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(4):Portable fire extinguishers were not kept in their designated places when not being used.  Location: Throughout the workshop and warehouse area.  a) On or about 10/26/2023, two fire extinguishers were found on the floor in an unmarked location next to a door between a wall and main entry stairwell.   b) On or about 10/26/2023, a fire extinguisher was found on the floor below the designated location on a hanger mounted to a support pole near the silk screening area of the workshop.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347063000.