INDIAN SPRINGS, NV —
OSHA Inspection: AMENTUM SERVICES, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AMENTUM SERVICES, INC. in 719 BOX CANYON ROAD, INDIAN SPRINGS, NV 89018 (NAICS 561210). OSHA activity number 347094625.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMENTUM SERVICES, INC.
- Site address
- 719 BOX CANYON ROAD
- City
- INDIAN SPRINGS
- State
- NV
- ZIP
- 89018
- Mailing
- 811 GRIER DRIVE SUITE A, LAS VEGAS, NV 89119
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 28
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.305 B01 II
- Issued
- Mar 13, 2024
- Penalty
- Initial $4,495 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed: On or about November 7, 2023, the employer did not ensure that all of the openings of the company's electrical breaker panels located in the east hangar of building 719, were effectively closed. Two electrical breaker panels identified as LP5 and PP2 had unused circuit breaker openings. Employees tasked with completing maintenance activities and others working in the immediate area were potentially exposed to electrical hazards if dust, dirt or other contaminates were to make contact with conductors creating an arc flash.
Recent events (2)
- — I (S) $0
- — Z (S) $4495
1910.37 B05
- Issued
- Mar 13, 2024
- Abate by
- Mar 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet): On or about November 7, 2023, personnel doors which are part of the aircraft hangar rolling door system were used as an exit and exit discharge during an emergency. The personnel doors were not properly illuminated and marked with signage used to notify employees and others accessing the area that the doors were "Not an Exit" was not attached to the doors thus potentially exposing employees to smoke and/or other fire hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 E03
- Issued
- Mar 13, 2024
- Abate by
- Mar 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: On or about November 7, 2023, the employer did not ensure that annual maintenance checks of portable fire extinguishers located throughout the facility were completed as required. Records with the name of the individual(s) who conducted the inspection and along with the date the inspection was completed were not retained and/or made available for review by a representative of the Secretary of Laborer.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Amentum Services, INC.
View Amentum Services, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 561210)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347094625.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.