OSHA Inspection: CREATIVE MODULAR CONSTRUCTION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CREATIVE MODULAR CONSTRUCTION in 2738 E KEARNEY ST, SPRINGFIELD, MO 65803 (NAICS 332311). OSHA activity number 347103293.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Creative Modular Construction — free Get an email when a new federal OSHA severe-injury report for Creative Modular Construction is published. One employer, no account, unsubscribe in one click.
Site address
2738 E KEARNEY ST
City
SPRINGFIELD
State
MO
ZIP
65803
Mailing
529 N PRINCE LN, SPRINGFIELD, MO 65802
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332311
Employees
150
Ownership type
A

5 citations on file for this inspection.

1910.252 B03

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Mar 27, 2024
Penalty
Initial $12,445 · Current $3,000 Reduced
29 CFR  1910.252(b)(3):Employees exposed to the hazards created by welding, cutting, or brazing operations were not protected by personal protective equipment in accordance with the requirements of 29 CFR 1910.132:   At a commercial worksite located at 2738 E Kearney Ste B, Springfield MO -- employees engaged in welding were not protected by fire retardant welding smocks. This exposed employees to burns and possible fire. This was documented on or about 11/13/2023.
Recent events (3)
  • — F (O) $3000
  • — C (S) $12445
  • — Z (S) $12445

1910.303 B02

Other-than-serious Gravity 5 2 instances 35 exposed
Issued
Mar 27, 2024
Penalty
Initial $8,296 · Current $1,000 Reduced
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  At a commercial worksite located at 2738 E Kearney Ste B, Springfield MO -- power strips were used to power saws and other heavy equipment that the power strips were not rated for. Additionally, power strips were plugged into extension cords (daisy chaining). This exposed employees to electrical shocks and/or burns. This was documented on or about 11/13/2023.
Recent events (3)
  • — F (O) $1000
  • — C (S) $8296
  • — Z (S) $8296

1910.305 B01 II

Other-than-serious Gravity 10 9 instances 35 exposed
Issued
Mar 27, 2024
Penalty
Initial $14,518 · Current $1,000 Reduced
29 CFR  1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed:  At a commercial worksite located at 2738 E Kearney Ste B, Springfield MO -- throughout facility there were numerous junction boxes with missing face plates and/or covers. This exposed employees to numerous electrical shocks and/or burns. This was documented on or about 11/13/2023.
Recent events (3)
  • — F (O) $1000
  • — C (S) $14518
  • — Z (S) $14518

1910.305 D02

Serious Gravity 10 2 instances 35 exposed
Issued
Mar 27, 2024
Abate by
Apr 22, 2024
Penalty
Initial $14,518 · Current $10,000 Reduced
29 CFR  1910.305(d)(2):Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:  At a commercial worksite located at 2738 E Kearney Ste B, Springfield MO -- breaker cabinets were not dead front exposing employees to electrical shocks and/or burns. This was documented on or about 11/13/2023.
Recent events (3)
  • — F (S) $10000
  • — C (S) $14518
  • — Z (S) $14518

1910.305 G02 III

Serious Gravity 5 4 instances 35 exposed
Issued
Mar 27, 2024
Penalty
Initial $10,372 · Current $0 Reduced
29 CFR  1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:   At a commercial worksite located at 2738 E Kearney Ste B, Springfield MO -- Flexible cords entering cabinets were not connected to fittings causing strain relief. This exposed employees to electrical shocks and/or burns. This was documented on or about 11/13/2023.