BROOKLYN, NY —
OSHA Inspection: GENESIS NYC CONSTRUCTION CORP
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of GENESIS NYC CONSTRUCTION CORP in 2106 77TH STREET, BROOKLYN, NY 11214 (NAICS 236118). OSHA activity number 347129512.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GENESIS NYC CONSTRUCTION CORP
- Site address
- 2106 77TH STREET
- City
- BROOKLYN
- State
- NY
- ZIP
- 11214
- Mailing
- 166-20 UNION TURNPIKE, FRESH MEADOWS, NY 11366
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236118
- Employees
- 3
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 B02
- Issued
- May 24, 2024
- Penalty
- Initial $2,765 · Current $1,770 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification. Location: 2106 77th Street, Brooklyn, NY. On or about 11/29/2023, a) Two 4x4 electrical metal boxes were used without mounted. They were installed with duplex outlets and used for energizing various electrical equipment. b) Two relocatable power taps were used at a construction site. They were used for used for energizing various electrical equipment.
Recent events (2)
- — I (S) $1770
- — Z (S) $2765
1926.403 I02 I
- Issued
- May 24, 2024
- Penalty
- Initial $4,839 · Current $3,000 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50-volts or more were not guarded against accidental contact. Location: 2106 77th Street, Brooklyn, NY. On or about 11/29/2023, a) Electrical breaker panels were not installed with the dead-front cover. Live electrical parts operating at 110-volts were not guarded from accidental contact.
Recent events (2)
- — I (S) $3000
- — Z (S) $4839
1926.404 F06
- Issued
- May 24, 2024
- Penalty
- Initial $4,839 · Current $3,000 Reduced
General-duty citation text
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous: Location: 2106 77th Street, Brooklyn, NY. On or about 11/29/2023, a) The path to ground of the temporary wiring circuit was not continuous. The 110-volt temporary wiring circuit did not have a grounding conductor.
Recent events (2)
- — I (S) $3000
- — Z (S) $4839
1926.405 G02 III
- Issued
- May 24, 2024
- Penalty
- Initial $3,457 · Current $2,230 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap. Location: 2106 77th Street, Brooklyn, NY. On or about 11/29/2023, a) The power cord of a Makita brand abrasive chop saw was repair with a splicing. Employees used the saw to cut cast iron pipes. b) A fabricated cord consisting of a pig-tail cord spliced to a BX cable was used to provide power for back feeding a breaker panel. Four of these fabricated cords were used at four separate breaker panels.
Recent events (2)
- — I (S) $2230
- — Z (S) $3457
More inspections in this industry (NAICS 236118)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347129512.