Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BEMER PETROLEUM CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BEMER PETROLEUM CORP. in 210 COMMERCE STREET, GLASTONBURY, CT 06033 (NAICS 454310). OSHA activity number 347139677.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bemer Petroleum Corp. — free Get an email when a new federal OSHA severe-injury report for Bemer Petroleum Corp. is published. One employer, no account, unsubscribe in one click.
Site address
210 COMMERCE STREET
City
GLASTONBURY
State
CT
ZIP
06033
Mailing
210 COMMERCE STREET, GLASTONBURY, CT 06033
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454310
Employees
15
Ownership type
A

23 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 15, 2024
Penalty
Initial $3,918 · Current $3,134 Reduced
OSH ACT of 1970 Section (5)(a)(1):  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to crushing hazards:  Dock and Storage Area:  On, or about, December 4, 2023, employees who operated the Nissan forklift did not use the restraint system (seatbelt).  It was secured behind the operator's seat.
Recent events (2)
  • — I (S) $3134.4
  • — Z (S) $3918

1910.26 C

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 15, 2024
Penalty
Initial $2,350 · Current $1,880 Reduced
29 CFR 1910.26(c): The employer did not ensure that portable dockboards  are secured by anchoring them in place or using equipment or devices that prevent the dockboard from moving out of a safe position:  Dock Building:  On, or about, December 4, 2023, the dockboard provided for use at the loading dock was not provided with a cleat or other means to secure the dockboard from being displaced when in use.
Recent events (2)
  • — I (S) $1880
  • — Z (S) $2350

1910.26 E

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 15, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.26(e):  The employer did not ensure that portable dockboards are equipped with handholds or other means to permit safe handling of dockboards:  Dock Building:  On, or about, December 4, 2024, the dockboard provided for use at the loading dock was not provided with handholds or handles to permit safe handling.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.28 B11 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
May 13, 2024
Penalty
Initial $3,687 · Current $2,950 Reduced
29 CFR 1910.28(b)(11)(ii): The employer did not ensure that each flight of stairs having at least 3 treads and at least 4 risers is equipped with stair rail systems and handrails as described in 29 CFR 1910.28 Table D-2-Stairway Handrail Requirements:  Dock Building:  On, or about, December 4, 2023, a stair rail was not provided on the left side, descending, on the set of stairs that provided access to the dock building on the side of the building facing the office building.
Recent events (2)
  • — I (S) $2949.6
  • — Z (S) $3687

1910.37 A03

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $6,452 · Current $5,162 Reduced
29 CFR 1910.37(a)(3):  Exit route(s) were not kept free and unobstructed:  Dock Building:  On, or about, December 4, 2023, an exit door and associated stairway provided in the room that housed the propane cylinder filling stations was completely blocked by stacked propane cylinders both on the interior and exterior of the building.
Recent events (2)
  • — I (S) $5161.6
  • — Z (S) $6452

1910.37 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):  Each exit was not clearly visible and marked by a sign reading "Exit":  Dock Building:  On, or about, December 4, 2023, an exit door provided in the room that housed the propane cylinder filling stations was not provided with an EXIT sign.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.101 B

Serious Gravity 10 30 instances 2 exposed
Issued
Feb 15, 2024
Abate by
Jul 12, 2024
Penalty
Initial $6,452 · Current $5,162 Reduced
29 CFR  1910.101(b):  The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  Ref. Section 3.7.7.2 and 3.7.4.1  Dock Building:  On, or about, December 4, 2023, compressed gas containers/cylinders were not stored securely in that:  1.	Cylinders were stored along walkways. 2.	Cylinders were not secured from falling by either a restraint or with three-point contact nesting. 3.	Cylinders were stored along the edge of the loading dock.
Recent events (2)
  • — I (S) $5161.6
  • — Z (S) $6452

1910.110 B06 VI

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $4,610 · Current $3,688 Reduced
29 CFR  1910.110(b)(6)(vi):  Readily ignitable material such as weeds and long dry grass was not removed within 10 feet of any container:  Storage Area:  On, or about, December 4, 2023, the area around the base of the 60,000 gallon and 30,000 gallon propane storage tanks was covered with dried leaves and dead, dried weeds.
Recent events (2)
  • — I (S) $3688
  • — Z (S) $4610

1910.119 C01

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $4,610 · Current $0 Reduced
29 CFR  1910.119(c)(1):  The employer did not develop a written plan of action regarding the implementation of the employee participation required by this paragraph:  Worksite:  On, or about, December 4, 2023, the employer had not developed a written plan of action to address how employee participation would be implemented in a Process Safety Management program where a large bulk liquified petroleum gas operation was in operation.
Recent events (3)
  • — F (S) $0
  • — C (S) $4610
  • — Z (S) $4610

1910.119 D02 I A

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $6,452 · Current $0 Reduced
29 CFR  1910.119(d)(2)(i)(A):  The employer did not include a block flow diagram or simplified process flow diagram as part of process safety information concerning technology of the process:  Worksite:  On, or about, December 4, 2023, the employer had not compiled Process Safety Information that related to the technology of the bulk liquified petroleum gas operation in that a block flow diagram had not been developed.
Recent events (3)
  • — F (S) $0
  • — C (S) $6452
  • — Z (S) $6452

1910.119 D03 I A

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.119(d)(3)(i)(A):  The employer did not complete a compilation of process safety information pertaining to the material of construction of equipment in the process:  Worksite:  On, or about, December 4, 2023, the employer had not compiled Process Safety Information that related to the equipment in the bulk liquified petroleum gas operation such as specifications for the piping system, pressure relief devices, hose, filling equipment and the nitrogen system.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 D03 I B

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(B):  The employer did not develop piping and instrument diagrams for the equipment that was part of the process:  Worksite:  On, or about, December 4, 2023, the employer had not compiled Process Safety Information that related to the equipment in the bulk liquified petroleum gas operation in that a piping and instrumentation diagram had not been developed.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 D03 I C

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(C):  Information pertaining to the equipment in the process did not include the electrical classification:  Worksite: On, or about, December 4, 2023, the employer had not compiled Process Safety Information that related to equipment in the bulk liquified petroleum gas operation in that areas around the bulk tanks, off-loading and filling stations had not been evaluated for proper electrical classification.  Although some areas appeared to have been provided with Class I wiring, vehicular traffic and truck parking was allowed in close proximity to bulk containers and filling stations.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 D03 I D

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.119(d)(3)(i)(D):  Information pertaining to equipment in the process did not include relief system design and design basis:  Worksite:  On, or about, December 4, 2023, the employer had not compiled Process Safety Information that related to the equipment in the bulk liquified petroleum gas operation in that data for the pressure relief valves and hydrostatic relief valves was not available.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 E01

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $6,452 · Current $0 Reduced
29 CFR  1910.119(e)(1):  The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119:  Worksite:  On, or about, December 4, 2023, the employer had not performed a Process Hazard Analysis of the bulk liquified petroleum gas operation.
Recent events (3)
  • — F (S) $0
  • — C (S) $6452
  • — Z (S) $6452

1910.119 F01

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $6,452 · Current $0 Reduced
29 CFR  1910.119(f)(1):  Written operating procedures providing clear instruction for conducting operations in a covered process safely and consistently with process safety information addressing all of the elements listed in 29 CFR 1910.119(f)(1)(i) through 29 CFR 1910.119(f)(1)(iv) have not been developed and implemented:  Worksite:  On, or about, December 4, 2023, the employer had not developed Operating Procedures for operations involving the bulk liquified petroleum gas operation.
Recent events (3)
  • — F (S) $0
  • — C (S) $6452
  • — Z (S) $6452

1910.119 J02

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $6,452 · Current $0 Reduced
29 CFR  1910.119(j)(2):  The employer did not establish or implement written procedures to maintain the on-going integrity of process equipment:  Worksite:  On, or about, December 4, 2023, the employer had not developed and implemented written mechanical integrity procedures that complied with recognized and generally accepted good engineering practices to ensure the on-going integrity of the bulk liquified petroleum operation including the bulk storage tanks, piping system, safety systems (nitrogen, sprinkler) and filling station equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $6452
  • — Z (S) $6452

1910.119 J04 I

Deleted Serious Gravity 10 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.119(j)(4)(i):  The employer did not perform inspection and tests on process equipment:  Worksite:  On, or about, December 4, 2023, the employer had not conducted inspections and tests to ensure the on-going integrity of the bulk liquified petroleum operation such as documented inspections and tests of the bulk storage tanks, pressure relief devices, piping systems, emergency systems such as sprinklers and nitrogen system, hoses and filling equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 N

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $3,687 · Current $0 Reduced
29 CFR  1910.119(n):  The employer did not establish an emergency plan for the entire plant in accordance with the provisions of 29 CFR 1910.38:  Worksite:  On, or about, December 4, 2023, the employer had not developed an Emergency Action Plan.
Recent events (3)
  • — F (S) $0
  • — C (S) $3687
  • — Z (S) $3687

1910.119 O01

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $4,610 · Current $0 Reduced
29 CFR  1910.119(o)(1):  The employer did not certify that they have evaluated compliance with the provisions of this section at least every three years:  Worksite:  On, or about, December 4, 2023, the employer had not conducted a Compliance Audit to ensure compliance with 29 CFR 1910.119 Process Safety Management of Highly Hazardous Chemicals.
Recent events (3)
  • — F (S) $0
  • — C (S) $4610
  • — Z (S) $4610

1910.178 C02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
Oct 15, 2024
Penalty
Initial $4,610 · Current $3,688 Reduced
29 CFR  1910.178(c)(2)(iv):  Power-operated industrial trucks designated as DY, EE, or EX were not used in locations where volatile flammable liquids or flammable gases are handled, processed or used, but in which the hazardous liquids, vapors or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems, or in the case of abnormal operation of equipment:   Dock and Storage Area:  On, or about, December 4, 2023, a Nissan Model CF01 forklift was used to transport pallets and cages of compressed gas cylinders, including those that contained LPG.  In addition to the transport of compressed gas cylinders, the travel area also included inlet/outlet filling stations for the bulk storage tanks and a cylinder fill station.  The Nissan forklift was listed as a Type LP on the identification plate and was not designed for use in a location where flammable gas could be present in the event of a release or malfunction.
Recent events (2)
  • — I (S) $3688
  • — Z (S) $4610

1910.178 L01 I

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
May 13, 2024
Penalty
Initial $2,765 · Current $2,212 Reduced
29 CFR  1910.178(l)(1)(i):  The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l):  Dock and Storage Area:  On, or about, December 4, 2023, employees who operated a Nissan forklift had not been provided forklift training.
Recent events (2)
  • — I (S) $2212
  • — Z (S) $2765

1910.178 P01

Other-than-serious 1 instance 2 exposed
Issued
Feb 15, 2024
Abate by
Apr 3, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.178(p)(1):  Powered industrial truck(s) found to be in need of repair, defective, or in any way unsafe had not been  taken out of service until restored to safe operating condition(s):  Dock and Storage Area:  On, or about, December 2, 2023, the weather cover that was attached to the overhead guard on the Nissan Model CF01 forklift obstructed the operator's view through the guard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Bemer Petroleum Corp.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347139677.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.