OSHA Inspection: USDA/FSIS

Unprogrammed Related inspection · Health discipline

On , OSHA opened an unprogrammed Related health inspection of USDA/FSIS in 3008 PENNS VALLEY PIKE, CENTRE HALL, PA 16828 (NAICS 926140). OSHA activity number 347166803.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usda/Fsis — free Get an email when a new federal OSHA severe-injury report for Usda/Fsis is published. One employer, no account, unsubscribe in one click.
Establishment
USDA/FSIS
Site address
3008 PENNS VALLEY PIKE
City
CENTRE HALL
State
PA
ZIP
16828
Mailing
701 MARKET ST., SUITE 4100-A, PHILADELPHIA, PA 19092
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926140
Employees
100
Ownership type
D

2 citations on file for this inspection.

1910.28 B03 IV

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Apr 18, 2024
Abate by
May 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.28(b)(3)(iv):  The employer did not provide that each employee be protected from falling into a ladderway floor hole or ladderway platform hole by a guardrail system and toeboards erected on all exposed sides, except at the entrance to the hole, where a self-closing gate or an offset must be used.  (a) 3008 Penns Valley Road, Centre Hall, PA; Entre Room, Tote Dumper - On or about October 30, 2023, employees accessing the tote dumper platform were not protected from falls of approximately 5 feet from the platform at the ladder opening with a self-closing gate or offset.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.38 D

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Apr 18, 2024
Abate by
May 7, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.38(d): The employer did not have and maintain an employee alarm system with a distinctive signal for each purpose so that it complied with the requirements of 1910.165:  (a) 3008 Penns Valley Road, Centre Hall, PA; Entre Room - On or about October 30, 2023, employees were exposed to hazards associated with the uncontrolled release of anhydrous ammonia's toxic vapors. The employer did not ensure that there were distinctive audible alarms for emergencies that require different actions such as ammonia release and/or fire at the facility.   Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.