Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALERT AMBULANCE SERVICE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALERT AMBULANCE SERVICE, INC. in 28 BLANCHARD PLACE, SOUTH KINGSTOWN, RI 02879 (NAICS 621910). OSHA activity number 347190118.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Alert Ambulance Service, INC. — free Get an email when a new federal OSHA severe-injury report for Alert Ambulance Service, INC. is published. One employer, no account, unsubscribe in one click.
Site address
28 BLANCHARD PLACE
City
SOUTH KINGSTOWN
State
RI
ZIP
02879
Mailing
28 BLANCHARD PLACE, SOUTH KINGSTOWN, RI 02879
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
621910
Employees
20
Ownership type
A

6 citations on file for this inspection.

1910.37 A04

Deleted Serious Gravity 10 2 instances 3 exposed
Issued
Mar 12, 2024
Abate by
Apr 25, 2024
Penalty
Initial $14,518 · Current $0 Reduced
29 CFR  1910.37(a)(4): Safeguards designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting) were not in proper working order at all times:  a) Break Room: On or about January 3, 2024, employees were exposed to fire hazards due to an emergency battery unit missing in the break room area.  b) Garage Area:  On or about January 3, 2024, employees were exposed to fire hazards due to an emergency battery unit missing in the garage area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14518

1910.37 B06

Serious Gravity 10 2 instances 3 exposed
Issued
Mar 12, 2024
Penalty
Initial $0 · Current $5,807
29 CFR  1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a) Garage Area Front Entrance:  On or about January 3, 2024, employees were exposed to fire hazards due to two exit lights not being properly illuminated.  b) Garage Area Rear Entrance:  On or about January 3, 2024, employees were exposed to fire hazards due to two exit lights not being properly illuminated.
Recent events (2)
  • — I (S) $5807.2
  • — Z (S) $0

1910.101 B

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 12, 2024
Penalty
Initial $12,445 · Current $4,978 Reduced
29 CFR  1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks was not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:   a) Garage Area: On or about January 3, 2024, employees were working in the garage area, in and around an unchained compressed gas cylinder where it was exposed to being knocked over and damaged, exposing employees to explosion and projectile hazards.
Recent events (2)
  • — I (S) $4978
  • — Z (S) $12445

1910.305 B01 I

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Mar 12, 2024
Penalty
Initial $14,518 · Current $0 Reduced
29 CFR  1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  a) Garage Area: On or about January 3, 2024, employees were exposed to electrical shock and burn hazards due to a 120-volt cord-cap not properly installed and exposing conductors.
Recent events (2)
  • — I (S) $0
  • — Z (S) $14518

1910.305 B02 I

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 12, 2024
Penalty
Initial $0 · Current $5,807
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   a) Break Room: On or about January 3, 2024, employees were exposed to electrical shock and burn hazards due to a 120 volt duplex receptacle that was in use without a cover plate.
Recent events (2)
  • — I (S) $5807.2
  • — Z (S) $0

1910.305 G01 IV A

Other-than-serious 1 instance 3 exposed
Issued
Mar 12, 2024
Abate by
Apr 25, 2024
Penalty
Initial $1,165 · Current $466 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a) Garage Area: On or about January 3, 2024, employees were exposed to electrical shock and burn hazards due to two extension cords being utilized as permanent wiring to provide voltage to two cord-reels above the vehicles.
Recent events (2)
  • — I (O) $466
  • — Z (O) $1165

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347190118.