S COFFEYVILLE, OK —
OSHA Inspection: STAR PIPE USA LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of STAR PIPE USA LLC in 500 W. 4TH STREET, S COFFEYVILLE, OK 74072 (NAICS 331511). OSHA activity number 347196768.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STAR PIPE USA LLC
- Site address
- 500 W. 4TH STREET
- City
- S COFFEYVILLE
- State
- OK
- ZIP
- 74072
- Mailing
- P.O. BOX 129, S COFFEYVILLE, OK 74072
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331511
- Employees
- 648
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.332 B02
- Issued
- Jun 21, 2024
- Abate by
- Jul 18, 2024
- Penalty
- Initial $12,676 · Current $7,600 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety: On or about December 28, 2023, in the Southwest Power Control Room, an unqualified employee was not properly trained on electrical related safety practices and handed a tool to an employee who was at an energized 480-volt electrical cabinet that had a side panel removed.
Recent events (2)
- — I (S) $7600
- — Z (S) $12676
1910.335 B02
- Issued
- Jun 21, 2024
- Abate by
- Jul 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(b)(2): Barricades were not used in conjunction with safety signs where it was necessary to prevent or limit employee access to work areas in which employees were exposed to uninsulated energized conductors or circuit parts: On or about December 28, 2023, in the Southwest Power Control Room, employees performed electrical work at an energized 480-volt electrical cabinet with no barricades to limit employee access to work areas with exposure to uninsulated energized conductors or circuit parts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 A01
- Issued
- Jun 21, 2024
- Abate by
- Jul 18, 2024
- Penalty
- Initial $15,211 · Current $9,125 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or near them, unless the employer could demonstrate that deenergizing introduced additional or increased hazards or was infeasible due to equipment design or operational limitations. On or about December 28, 2023, in the Southwest Power Control Room, employees performed electrical work at an energized 480-volt electrical cabinet without demonstrating that de-energizing the electrical cabinet introduced additional or increased hazards or was infeasible.
Recent events (2)
- — I (S) $9125
- — Z (S) $15211
1910.335 A02 I
- Issued
- Jun 21, 2024
- Abate by
- Jul 18, 2024
- Penalty
- Initial $15,211 · Current $9,125 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: On or about December 28, 2023, in the Southwest Power Control Room, employees brought a conductive tool near an open side of an energized 480-volt electrical cabinet where there were exposed electrical parts.
Recent events (2)
- — I (S) $9125
- — Z (S) $15211
More inspections at Star Pipe USA LLC
View Star Pipe USA LLC's full OSHA safety record →
More inspections in this industry (NAICS 331511)
More inspections in OK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347196768.