PROVIDENCE, RI —
OSHA Inspection: LASALLE BAKERY, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LASALLE BAKERY, INC. in 685 ADMIRAL STREET, PROVIDENCE, RI 02908 (NAICS 311812). OSHA activity number 347204984.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LASALLE BAKERY, INC.
- Site address
- 685 ADMIRAL STREET
- City
- PROVIDENCE
- State
- RI
- ZIP
- 02908
- Mailing
- 685 ADMIRAL STREET, PROVIDENCE, RI 02908
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311812
- Employees
- 25
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 B01 II
- Issued
- Mar 12, 2024
- Penalty
- Initial $5,143 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: a) Walk-in Cooler: On or about January 11, 2024, employees were exposed to electrical shock and burn hazards due to a liquid-tight 90 degree connector that was broken and exposing the electrical conductors, utilized for the lighting inside the walk-in cooler.
Recent events (2)
- — I (S) $1500
- — Z (S) $5143
1910.303 G01 II
- Issued
- Mar 12, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage: a) First Floor Electrical Panels: On or about January 11, 2024, employees were exposed to electrical hazards due to electrical panels that were blocked by milk crates and a rolling shelf.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Mar 12, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: a) Dutchess Electrical Press: On or about January 11, 2024, employees were exposed to electrical hazards due to two SJ type cords, passing through the drop ceiling, powering the press.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Lasalle Bakery, INC.
View Lasalle Bakery, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311812)
More inspections in RI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347204984.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.