VAN BUREN, AR ·
OSHA Inspection: DAVIS IRON & METAL, INC.
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of DAVIS IRON & METAL, INC. in 611 S 23RD ST, VAN BUREN, AR 72956 (NAICS 423930). OSHA activity number 347218455.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DAVIS IRON & METAL, INC.
- Site address
- 611 S 23RD ST
- City
- VAN BUREN
- State
- AR
- ZIP
- 72956
- Mailing
- 2610 WHEELER AVENUE, FORT SMITH, AR 72901
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 8
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
5(a)(1)
- Issued
- Jul 8, 2024
- Abate by
- Aug 1, 2024
- Penalty
- Initial $11,292 · Current $11,292
2150
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a fire hazard: a) On or about January 9, 2024, employees were operating a Mr. Heater Gas Fired Infra-Red Tank Top Propane Heater, model MH 42T, while not maintaining a safe distance from the heater.
Recent events (2)
- · I (S) $11292
- · Z (S) $11292
1910.110 B06 VI
- Issued
- Jul 8, 2024
- Abate by
- Jul 16, 2024
- Penalty
- Initial $11,292 · Current $8,469 Reduced
General-duty citation text
29 CFR 1910.110(b)(6)(vi): Readily ignitable material such as weeds and long dry grass was not removed within 10 feet of any container: a) On or about January 18, 2024, on the north side of the building, there was combustible vegetation within 10-feet of the 1000-gallon propane tank.
Recent events (2)
- · I (S) $8469
- · Z (S) $11292
1910.110 B06 I
- Issued
- Jul 8, 2024
- Abate by
- Aug 12, 2024
- Penalty
- Initial $11,292 · Current $8,469 Reduced
General-duty citation text
29 CFR 1910.110(b)(6)(i): Containers and first stage regulating equipment of liquid petroleum gases were not located outside of the building: a) On or about January 18, 2024, north storage bay, the supply tank for the Mr. Heater Vent-Free Liquid Propane Radiant Heater used in the breakroom was stored inside the building.
Recent events (2)
- · I (S) $8469
- · Z (S) $11292
1910.110 B09 VII B
- Issued
- Jul 8, 2024
- Abate by
- Aug 12, 2024
- Penalty
- Initial $6,453 · Current $0 Reduced
General-duty citation text
29 CFR 1910.110(b)(9)(vii)(b): For use inside buildings the hose was not of minimum practical length, but exceeded 6 feet except as provided in paragraph (c)(5)(i)(g) of this section and extended from one room to another, or passed through any walls, partitions, ceilings, or floors: a) On or about January 18, 2024, a Mr. Heater Vent-Free Liquid Propane Radiant Heater was used in a breakroom where the propane supply hose passed through an interior brick wall.
Recent events (2)
- · I (S) $0
- · Z (S) $6453
1910.157 C01
- Issued
- Jul 8, 2024
- Abate by
- Jul 16, 2024
- Penalty
- Initial $9,680 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: On or about January 18, 2024, employees were engaged in work activities related to receiving and sorting scrap material where: a) a fire extinguisher sitting on a shelf in the buyer's bay to the right of office door was not mounted. b) a fire extinguisher sitting on a shelf in the buyer's bay to the right of office door. c) a fire extinguisher sitting on the table just inside office to the right of door leading to buyer's bay was not mounted.
Recent events (2)
- · I (S) $2500
- · Z (S) $9680
1910.1200 F06 I
- Issued
- Jul 8, 2024
- Abate by
- Jul 16, 2024
- Penalty
- Initial $9,680 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.1200(f)(6)(i): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v): a) On or about January 9, 2024, in the buyer's bay, employees were operating a Mr. Heater Gas Fired Infra-Red Tank Top Propane Heater with unmarked 20-pound propane container. b) On or about January 18, 2024, in the north storage room, a Mr. Heater Vent-Free Liquid Propane Radiant Heater was operated with an unmarked 100-pound propane container.
Recent events (2)
- · I (S) $2500
- · Z (S) $9680
More inspections in this industry (NAICS 423930)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 347218455.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.