Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CONTROLTEK, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONTROLTEK, INC. in 3505 AIRPORT ROAD, JONESBORO, AR 72401 (NAICS 335314). OSHA activity number 347226854.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Controltek, INC. — free Get an email when a new federal OSHA severe-injury report for Controltek, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
CONTROLTEK, INC.
Site address
3505 AIRPORT ROAD
City
JONESBORO
State
AR
ZIP
72401
Mailing
P.O. BOX 17006, JONESBORO, AR 72403
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335314
Employees
6
Ownership type
A

6 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 2 instances 2 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $11,292 · Current $7,904 Reduced
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:   a) On or about January 15, 2024, employees performing electrical work on an energized busbar system were not qualified to work on energized equipment.  b) On or about January 15, 2024, employees assigned fire watch duties were provided fire extinguishers.  The employees did not have fire extinguisher training.
Recent events (2)
  • — I (S) $7904.4
  • — Z (S) $11292

1926.97 C02 VIII

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $8,067 · Current $5,647 Reduced
29 CFR 1926.97(c)(2)(viii):  Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests were not in accordance with Table E-4 and Table E-5:   On or about January 15, 2024, employees were performing electrical work on an energized busbar system using rubber gloves without having electrical tests in the last six months.
Recent events (2)
  • — I (S) $5646.9
  • — Z (S) $8067

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $11,292 · Current $7,904 Reduced
29 CFR 1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work:    On or about January 15, 2024, employees performed electrical work such as but not limited to removing busplugs from an energized busbar system.
Recent events (2)
  • — I (S) $7904.4
  • — Z (S) $11292

1926.416 A03

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $11,292 · Current $7,904 Reduced
29 CFR 1926.416(a)(3): The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take:   On or about January 15, 2024, employees performed electrical work on energized busbar system.  Warning signs were not posted, and employees were not advised of the protective measures that need to be taken.
Recent events (2)
  • — I (S) $7904.4
  • — Z (S) $11292

1926.95 A

Serious Gravity 10 2 instances 2 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $11,292 · Current $7,904 Reduced
29 CFR  1926.95(a): Personal protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, or maintained in a sanitary and reliable condition it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation, or physical contact:  On or about January 15, 2024, employees were performing electrical work on an energized busbar system without electrical protective equipment, in that:  a) Employees were not wearing appropriate electrical protective equipment on the torso.  b) Employee were not wearing electrical protective equipment on the lower extremities.
Recent events (2)
  • — I (S) $7904.4
  • — Z (S) $11292

1926.102 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jul 15, 2024
Abate by
Sep 16, 2024
Penalty
Initial $11,292 · Current $0 Reduced
29 CFR 1926.102(a)(1): The employer did not ensure that each affected employee used appropriate eye or face protection when exposed to eye or face hazards from flying particles, molten metal, liquid chemicals, acids or caustic liquids, chemical gases or vapors, or potentially injurious light radiation:   On or about January 15, 2024, employees were performing electrical work on an energized busbar system without electrical protective equipment for their eyes and face.
Recent events (2)
  • — I (S) $0
  • — Z (S) $11292

View Controltek, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347226854.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.