PLEASANT PLAINS, IL —
OSHA Inspection: RCM COOPERATIVE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of RCM COOPERATIVE in 300 N. WASHINGTON STREET, PLEASANT PLAINS, IL 62677 (NAICS 493130). OSHA activity number 347250011.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RCM COOPERATIVE
- Site address
- 300 N. WASHINGTON STREET
- City
- PLEASANT PLAINS
- State
- IL
- ZIP
- 62677
- Mailing
- 26352 QUARRY AVE, ATHENS, IL 62613
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493130
- Employees
- 5
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.29 B13 I
- Issued
- Jul 10, 2024
- Penalty
- Initial $6,452 · Current $3,871 Reduced
General-duty citation text
29 CFR 1910.29(b)(13)(i): The guardrail system opening used around holes that serve as points of access (such as ladderways), did not have a self-closing gate that slides or swings away from the hole, and was equipped with a top rail and midrail or equivalent intermediate member that met the requirements in paragraph (b) of this section: On or about February 1, 2024, and at time prior, employees were exposed to fall hazards and guardrail systems used around openings that serve as points of access for fixed ladders were not equipped with a self-closing gate that slides or swings away from the opening on ladders located in areas including but not limited to: a. Bin 1 entry platform; b. Bin 4 entry platform; c. Bin 11 entry platform; d. Bin 12 entry platform; e. Bin 16 entry platform; f. Bin 17 entry platform; g. Bin 17 maintenance platform; h. Bin 17 loading platform.
Recent events (2)
- — I (S) $3871
- — Z (S) $6452
1910.212 A03 II
- Issued
- Jul 10, 2024
- Abate by
- Aug 15, 2024
- Penalty
- Initial $4,610 · Current $0 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle: On or about February 1, 2024, employees were exposed to amputation and entanglement hazards when operating the Bin 13 swing auger due to large openings in the guarding.
Recent events (2)
- — I (S) $0
- — Z (S) $4610
1910.303 B07 IV
- Issued
- Jul 10, 2024
- Abate by
- Aug 15, 2024
- Penalty
- Initial $3,687 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. On or about February 1, 2024, employees were exposed to electrical shock and the employer failed to ensure the conduit protecting the wiring running into the main panel box located in the MCC were not damaged.
Recent events (2)
- — I (O) $0
- — Z (S) $3687
1910.303 F02
- Issued
- Jul 10, 2024
- Abate by
- Aug 15, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about February 1, 2024, the employer did not ensure each circuit breaker was identified in the main panel box located in the MCC were not legibly marked to indicate its purpose. This condition exposed the employees to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 H02 V D
- Issued
- Jul 10, 2024
- Abate by
- Aug 15, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(h)(2)(v)(D): Where nonmetallic or metal-enclosed equipment is accessible to the general public and the bottom of the enclosure is less than 2.44 m (8.0 ft) above the floor or grade level, the enclosure door or hinged cover was not kept locked: On or about February 1, 2024, the employer failed to ensure the dryer control panel located in an area accessible to the general public was locked.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 493130)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347250011.