CRESCENT CITY, FL —
OSHA Inspection: TRUE HOUSE, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of TRUE HOUSE, INC. in 105 DENVER ROAD, CRESCENT CITY, FL 32112 (NAICS 321214). OSHA activity number 347266074.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TRUE HOUSE, INC.
- Site address
- 105 DENVER ROAD
- City
- CRESCENT CITY
- State
- FL
- ZIP
- 32112
- Mailing
- 9000 REGENCY SQUARE BLVD, STE 100, JACKSONVILLE, FL 32211
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321214
- Employees
- 81
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.22 A03
- Issued
- Apr 9, 2024
- Penalty
- Initial $5,288 · Current $3,173 Reduced
General-duty citation text
29 CFR 1910.22(a)(3): The employer did not ensure that walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice: a. Steel Top Table 2: On or about 02/07/2024, the stairs used by employees had a broken step, exposing employees to fall hazards and leg injuries.
Recent events (2)
- — I (S) $3172.8
- — Z (S) $5288
1910.305 B02 I
- Issued
- Apr 9, 2024
- Penalty
- Initial $5,288 · Current $3,173 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a. HD incline Conveyor: On or about 02/07/2024, the employer exposed employees to an electrical shock hazard from the outlet box located underneath the conveyor that did not have a faceplate. b. In the outside shed: On or about 02/07/2024, at the power receptacle, the employer exposed employees to an electrical shock hazard in that the receptacle box cover was not covered with a faceplate identified for a receptacle, allowing conductors to be accessible and an opening in the box.
Recent events (2)
- — I (S) $3172.8
- — Z (S) $5288
1910.303 B07 III
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iii): Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. a. HD incline Conveyor: On or about 02/07/2024, the employer exposed employees working at the conveyor with fire and electrical flash hazards from an accumulation of foreign debris of organic flammable material inside the electrical housing unit underneath the conveyor that had not been cleaned.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 I
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: a. West Side Stacker Area: On or about 02/07/2024, the employer exposed employees to an electrical shock hazard from the outlet box located on the wall that did not have the correct faceplate.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasions: a. HD incline Conveyor: On or about 02/07/2024, conductors entering an electrical housing box located underneath the conveyor were not protected from abrasion.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B01 I
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(1)(i): Electric equipment was not suitable for installation and use in conformity with the provisions of this subpart and not free from recognized hazards that are likely to cause death or serious physical harm to employees. a. West Side Stacker Area: On or about 02/07/2024, a relocatable power tap was used in the metal shed outside the plant to power portable electrical heaters, a practice not approved by the manufacturer.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 A02 IX
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ix):Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard: a. West Side Stacker Area: On or about 02/07/2024, a lamp was not protected from accidental contact.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Apr 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were used As a substitute for the fixed wiring of a structure for uses that are not specifically permitted in paragraph (g)(1)(ii) of this section: a. West Side Stacker Area: On or about 02/07/2024, a flexible cord was run through the metal wall to power heaters and lighting.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at True House, INC.
View True House, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321214)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347266074.