Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MOKON THERMAL FLUID SYSTEMS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MOKON THERMAL FLUID SYSTEMS in 2150 ELMWOOD AVENUE, BUFFALO, NY 14207 (NAICS 333249). OSHA activity number 347324840.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mokon Thermal Fluid Systems — free Get an email when a new federal OSHA severe-injury report for Mokon Thermal Fluid Systems is published. One employer, no account, unsubscribe in one click.
Site address
2150 ELMWOOD AVENUE
City
BUFFALO
State
NY
ZIP
14207
Mailing
2150 ELMWOOD AVENUE, BUFFALO, NY 14207
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333249
Employees
81
Ownership type
A

2 citations on file for this inspection.

1910.110 F02 II

Serious Gravity 1 1 instance 4 exposed
Issued
Mar 14, 2024
Abate by
Apr 5, 2024
Penalty
Initial $3,496 · Current $2,622 Reduced
29 CFR  1910.110(f)(2)(ii): Liquefied petroleum gas container(s) stored inside were located near exits, stairways, or in areas normally used or intended for the safe exit of people:  a) On or about 03/05/2024 in the production area; where a cylinder of propane, used as fuel for the fork truck, was stored under the stairs used to access the mezzanine.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $2622
  • — Z (S) $3496

1910.253 B04 III

Serious Gravity 1 1 instance 5 exposed
Issued
Mar 14, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  a) On or about 03/05/2024, in the production area; where a cylinder of acetylene (tagged as MT) was stored within 4 feet of oxygen cylinders.   NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347324840.