PORTLAND, ME —
OSHA Inspection: FREEDOM FISH, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FREEDOM FISH, LLC in 450 COMMERCIAL STREET, PORTLAND, ME 04101 (NAICS 311710). OSHA activity number 347328304.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FREEDOM FISH, LLC
- Site address
- 450 COMMERCIAL STREET
- City
- PORTLAND
- State
- ME
- ZIP
- 04101
- Mailing
- 450 COMMERCIAL STREET, PORTLAND, ME 04101
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311710
- Employees
- 11
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.305 B02 I
- Issued
- Mar 18, 2024
- Penalty
- Initial $4,610 · Current $2,305 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Walk-in Cooler - The 120-volt junction box did not contain a cover.
Recent events (2)
- — I (S) $2305
- — Z (S) $4610
1910.305 G01 IV A
- Issued
- Mar 18, 2024
- Penalty
- Initial $4,610 · Current $2,305 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Packing Area - A commercial fish smoking oven and two weight scales, in use for over a year, were powered by extension cords.
Recent events (2)
- — I (S) $2305
- — Z (S) $4610
1910.305 G01 IV B
- Issued
- Mar 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: Packaging Area and Lobster Tanks Area - Extension cords used to power scales and other appliances were run through and under the drop ceiling tiles.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 E02
- Issued
- Mar 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: Establishment - All fire extinguishers (6), located throughout the facility, were not inspected at least monthly.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 A05
- Issued
- Mar 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(a)(5): The powered industrial truck was equipped with front-end attachments other than factory installed attachments, however the employer did not request that the truck be marked to identify the attachments and show the approximate weight of the truck and attachment combination at maximum elevation with load laterally centered: Establishment - The Doosan forklift model number G18S-5, fitted with a Totall brand rotating attachment, was not equipped with a data plate containing revised capacities.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.178 L04 III
- Issued
- Mar 18, 2024
- Abate by
- May 2, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years: Establishment - The operator of the Doosan and Toyota counterbalance lifts had not been evaluated at least once every three years.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Mar 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Delivery and Receiving Area, Adjacent to Rollup Door - Employer did not ensure that the areas in front of energized electrical panels and freezer knife switch were cleared of material, including boxes of packing material and miscellaneous equipment.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 311710)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347328304.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.