Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FREEDOM FISH, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FREEDOM FISH, LLC in 450 COMMERCIAL STREET, PORTLAND, ME 04101 (NAICS 311710). OSHA activity number 347328304.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Freedom Fish, LLC — free Get an email when a new federal OSHA severe-injury report for Freedom Fish, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
FREEDOM FISH, LLC
Site address
450 COMMERCIAL STREET
City
PORTLAND
State
ME
ZIP
04101
Mailing
450 COMMERCIAL STREET, PORTLAND, ME 04101
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311710
Employees
11
Ownership type
A

7 citations on file for this inspection.

1910.305 B02 I

Serious Gravity 5 1 instance 11 exposed
Issued
Mar 18, 2024
Penalty
Initial $4,610 · Current $2,305 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  Walk-in Cooler - The 120-volt junction box did not contain a cover.
Recent events (2)
  • — I (S) $2305
  • — Z (S) $4610

1910.305 G01 IV A

Serious Gravity 5 3 instances 11 exposed
Issued
Mar 18, 2024
Penalty
Initial $4,610 · Current $2,305 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Packing Area - A commercial fish smoking oven and two weight scales, in use for over a year, were powered by extension cords.
Recent events (2)
  • — I (S) $2305
  • — Z (S) $4610

1910.305 G01 IV B

Serious Gravity 5 3 instances 11 exposed
Issued
Mar 18, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  Packaging Area and Lobster Tanks Area - Extension cords used to power scales and other appliances were run through and under the drop ceiling tiles.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 E02

Other-than-serious 6 instances 11 exposed
Issued
Mar 18, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  Establishment - All fire extinguishers (6), located throughout the facility, were not inspected at least monthly.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 A05

Other-than-serious 1 instance 1 exposed
Issued
Mar 18, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.178(a)(5): The powered industrial truck was equipped with front-end attachments other than factory installed attachments, however the employer did not request that the truck be marked to identify the attachments and show the approximate weight of the truck and attachment combination at maximum elevation with load laterally centered:  Establishment - The Doosan forklift model number G18S-5, fitted with a Totall brand rotating attachment, was not equipped with a data plate containing revised capacities.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 L04 III

Other-than-serious 1 instance 1 exposed
Issued
Mar 18, 2024
Abate by
May 2, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:  Establishment - The operator of the Doosan and Toyota counterbalance lifts had not been evaluated at least once every three years.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 11 exposed
Issued
Mar 18, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Delivery and Receiving Area, Adjacent to Rollup Door - Employer did not ensure that the areas in front of energized electrical panels and freezer knife switch were cleared of material, including boxes of packing material and miscellaneous equipment.