AUSTIN, TX —
OSHA Inspection: G.A.M.A., LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of G.A.M.A., LLC in 8801 RESEARCH BLVD, AUSTIN, TX 78758 (NAICS 452311). OSHA activity number 347342495.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- G.A.M.A., LLC
- Site address
- 8801 RESEARCH BLVD
- City
- AUSTIN
- State
- TX
- ZIP
- 78758
- Mailing
- 8801 RESEARCH BLVD, AUSTIN, TX 78758
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452311
- Employees
- 30
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.22 A01
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. On or about March 13, 2024, and at times prior thereto, employees were exposed to a slip hazard from the accumulation of ice and water outside a walk-in freezer.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.37 A03
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exits routes were not maintained to provide free and unobstructed access. On or about March 13, 2024, and at times prior thereto, employees were exposed to a fire hazard by a partially blocked emergency exit door.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.151 C
- Issued
- May 24, 2024
- Abate by
- Jun 21, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: On or about March 13, 2024, and at times prior thereto, employees were exposed to a chemical hazard from corrosive batteries without a eyewash station.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.157 C01
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): A portable fire extinguishers were blocked or missing and not available for immediate use by employees. On or about March 13, 2024, and at times prior thereto, employees were exposed to a fire hazard due to blocked fire extinguishers.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.303 B02
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. On or about March 13, 2024, and at times prior thereto, employees were exposed to an electrical hazard from electrical equipment not being used in accordance with the manufacturer's instructions.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.303 C03 I
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.303(c)(3)(i): Conductors were not spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices were not spliced or joined mechanically and electrically secured first without solder and then soldered. All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose. On or about March 13, 2024, and at times prior thereto, employees were exposed to an electrical hazard due to spliced electrical cords.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.304 F01 IV
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Over-current devices were not readily accessible to each employee or authorized building management personnel. On or about March 13, 2024, and at times prior thereto, employees were exposed to an electrical hazard from breaker boxes and emergency knife switches being blocked from ready access.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
1910.334 A03 II
- Issued
- May 24, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.334(a)(3)(ii): Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles and/or altered to allow the grounding pole of a plug to be inserted into slots intended for connection-carrying conductors. On or about March 13, 2024, and at times prior thereto, employees were exposed to an electrical hazard due to the grounding conductor being bypassed.
Recent events (2)
- — I (S) $3733.2
- — Z (S) $6222
More inspections in this industry (NAICS 452311)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347342495.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.