ST THOMAS, VI —
OSHA Inspection: MOUNTAIN TOP
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MOUNTAIN TOP in 7840 MOUNTAIN TOP SAINT PETER MOUNTAIN ROAD, ST THOMAS, VI 00802 (NAICS 453220). OSHA activity number 347358285.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MOUNTAIN TOP
- Site address
- 7840 MOUNTAIN TOP SAINT PETER MOUNTAIN ROAD
- City
- ST THOMAS
- State
- VI
- ZIP
- 00802
- Mailing
- 7840 MOUNTAIN TOP SAINT PETER MOUNTAIN ROAD, ST THOMAS, VI 00802
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 453220
- Employees
- 21
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.36 G02
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $3,318 · Current $1,825 Reduced
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a. On or about March 20, 2024, at the main storage (shipping containers) area. The measurements throughout various points along the exit access of several containers and main access area ranged from 12 inches to 24 inches. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (S) $1824.9
- — Z (S) $3318
1910.303 B02
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $2,489 · Current $1,369 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about March 20, 2024, at the snacks vending area. Electrical equipment such as relocatable power tap (RPT) and extension cord were used in place of fixed firing to provide power to various kitchen appliances, exposing employees to electrical and fire hazards as follows: a. A seven-outlet relocatable power tap/power strip surge protector, Commercial Electric, model YLPT 45-2 (15- amp) was used to provide power to kitchen appliances such as toaster oven (12.5-amp); Omcan coffee percolator (12.5-amp) and Nutty Bavarian NBR2000 Plus electric peanut roaster (15.4-amp). b. A 20-ft extension cord was used to provide power to a Coca-Cola beverages cooler. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (S) $1368.95
- — Z (S) $2489
1910.305 B02 I
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $2,489 · Current $1,369 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On or about March 20, 2024, electrical receptacles used as power source were not fully-covered with a face plate cover as follows: a. At the lunch break area, the two-outlets electrical receptacle available for use had its cover lose, exposing conductors. b. At the snacks area, the two-outlets electrical receptacle used for to connect an extension cord for the kitchen appliances had its cover lose, exposing conductors. NOTE 1: Certification of abatement is not required for Instance (a) since it was submitted prior to citation issuance. NOTE 2 : Certification and documentation of abatement must be submitted for Instance (b) this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (S) $1368.95
- — Z (S) $2489
1910.305 C04
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $2,489 · Current $1,369 Reduced
General-duty citation text
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: a. On or about March 20, 2024, at the drink's storage area. Employees are exposed to an electric shock from a light switch with exposed conductors that did not have a face plate cover. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (S) $1368.95
- — Z (S) $2489
1910.157 C01
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $466 · Current $256 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries On or about March 20, 2024, fully-charged Class ABC 5-lbs portable fire extinguishers were not mounted as follows: a. At the snacks bar area next to the Coca-Cola cooler, portable fire extinguisher placed at floor level behind trash can. b. At the main cash registers area, portable fire extinguisher placed at floor level behind merchandise rack. c. At the main cash registers area, portable fire extinguisher placed on top of counter behind merchandise display rack. d. At the main entrance next to an exit door, a wall-mounted portable fire extinguisher was obstructed by marine metal decorations such as two ship bells. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (O) $256
- — Z (O) $466
1910.303 G01
- Issued
- Aug 28, 2024
- Abate by
- Sep 19, 2024
- Penalty
- Initial $466 · Current $256 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a. On or about March 20, 2024, at the drink's storage area. An electrical service panel was not readily accessible as a large wood two-shelve storage unit was installed beneath the panel. NOTE: Certification and documentation of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c) and (d), respectively.
Recent events (2)
- — I (O) $256
- — Z (O) $466
More inspections at Mountain TOP