OSHA Inspection: PRESTON REFRIGERATION CO., INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of PRESTON REFRIGERATION CO., INC. in 1400 NORTH WEBER AVENUE, SIOUX FALLS, SD 57103 (NAICS 423740). OSHA activity number 347380693.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Preston Refrigeration CO., INC. — free Get an email when a new federal OSHA severe-injury report for Preston Refrigeration CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
1400 NORTH WEBER AVENUE
City
SIOUX FALLS
State
SD
ZIP
57103
Mailing
6100 STILWELL STREET, KANSAS CITY, MO 64120
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423740
Employees
25
Ownership type
A

4 citations on file for this inspection.

1910.119 H03 IV

Other-than-serious Gravity 10 4 instances 7 exposed
Issued
Sep 10, 2024
Abate by
Oct 10, 2024
Penalty
Initial $14,518 · Current $10,000 Reduced

Hazardous substances 0170

29 CFR  1910.119(h)(3)(iv): The contract employer did not assure that each contract employee follows the safety rules of the facility including the safe work practices required by paragraph (f)(4) of this section such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel:  (a)Preston Refrigeration Co., Inc. at 1400 North Weber Avenue, Sioux Falls, SD 57103: On or about and at times prior to March 27, 2024, the employer did not adequately implement safe work practices in that the company did not follow the host employer line break policy prior to breaking the line to remove Evaporator 0205 from the ammonia system.  This condition exposed employees to anhydrous ammonia.
Recent events (3)
  • — F (O) $10000
  • — C (S) $14518
  • — Z (S) $14518

1910.147 C04 I

Deleted Serious Gravity 10 1 instance 7 exposed
Issued
Sep 10, 2024
Abate by
Oct 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 0170

29 CFR  1910.147(c)(4)(i):Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  (a)Preston Refrigeration Co., Inc. at 1400 North Weber Avenue, Sioux Falls, SD 57103: On or about and at times prior to March 27, 2024, the employer did not ensure that employees utilized written lockout/tagout procedures prior to performing a line break on Evaporator 0205.   This condition exposed employees to anhydrous ammonia.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 E03

Other-than-serious Gravity 10 4 instances 7 exposed
Issued
Sep 10, 2024
Abate by
Oct 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 0170

29 CFR 1910.119(e)(3): The process hazard analysis shall address the elements of (i) through (vii) of this paragraph:   (a)Preston Refrigeration Co., Inc. at 1400 North Weber Avenue, Sioux Falls, SD 57103: On or about and at times prior to March 27, 2024, the employer did not ensure that employees conducting line break activities on Evaporator 0205 had conducted an effective process hazard analysis prior to line break activities being conducted.  This condition exposed employees to anhydrous ammonia.  (i) The hazards of the process; (ii) The identification of any previous incident which had a likely potential for catastrophic consequences in the workplace; (iii) Engineering and administrative controls applicable to the application of detection methodologies to provide early warning of releases.  (Acceptable detection methods might include process monitoring and control instrumentation with alarms, and detection hardware such as hydrocarbon sensors.); (iv) Consequences of failure of engineering and administrative controls; (v) Facility siting; (vi) Human Factors; and (vii) A qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace.
Recent events (3)
  • — F (O) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 D04 I

Deleted Serious Gravity 10 7 instances 7 exposed
Issued
Sep 10, 2024
Abate by
Oct 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 0170

29 CFR  1910.147(d)(4)(i):Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:  (a)Preston Refrigeration Co., Inc. at 1400 North Weber Avenue, Sioux Falls, SD 57103:  On or about and at times prior to March 27, 2024, the employer did not ensure that lockout or tagout devices were affixed to each energy isolating device prior to conducting line breaking activities on Evaporator 0205.  This condition exposed employees to anhydrous ammonia.  The following energy isolating devices required a lockout device:  (i) Hot gas stop valve VH101-2080; (ii) Solenoid valve VO103-0064; (iii) MVP stop valve VL101-0205; (iv) MVP solenoid stem valve; (v) Pump out valve VP101-2080; (vi) Vent valve VV102-0205; (vii) Safety relief valve (VF-101-0205)
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Preston Refrigeration CO., INC.'s full OSHA safety record →