OSHA Inspection: BLACK DIAMOND POWER COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BLACK DIAMOND POWER COMPANY in 101 ROBERT C. BYRD DRIVE, SOPHIA, WV 25921 (NAICS 221122). OSHA activity number 347388233.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Black Diamond Power Company — free Get an email when a new federal OSHA severe-injury report for Black Diamond Power Company is published. One employer, no account, unsubscribe in one click.
Site address
101 ROBERT C. BYRD DRIVE
City
SOPHIA
State
WV
ZIP
25921
Mailing
PO BOX 276, SOPHIA, WV 25921
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
20
Ownership type
A

4 citations on file for this inspection.

1910.137 C02 VIII

Serious Gravity 10 1 instance 4 exposed
Issued
Sep 27, 2024
Abate by
Oct 17, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests.  (a) Sophia Shop/Office: On April 26, 2024 and times prior, employees used rubber insulated gloves when working on or near primary power sources of up to 12,470 volts that were not electrically tested every six months, exposing employees to electric shock injuries and/or electrocution.
Recent events (1)
  • — Z (S) $6452

1910.137 C02 II

Serious Gravity 10 1 instance 4 exposed
Issued
Sep 27, 2024
Abate by
Oct 9, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.137(c)(2)(ii): The employer did not require an air test of electrically rated gloves daily or prior to each shift.  (a) Sophia Shop/Office: On April 26, 2024 and times prior, employees did not perform the daily air tests or visual inspection of the rubber insulated gloves, exposing the employees to electric shock injuries and/or electrocution.
Recent events (1)
  • — Z (S) $0

1910.67 C02 XI

Serious Gravity 10 1 instance 4 exposed
Issued
Sep 27, 2024
Abate by
Oct 17, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR 1910.67(c)(2)(xi): The insulated portion of an aerial lift was altered, reducing its insulating value.  (a) Sophia Shop/Office: On April 9, 2024 and times prior, employees used a 2012 International truck with a Terex Hi-Ranger aerial lift bucket that was cracked and damaged, reducing the effectiveness of the insulating properties and exposing the employees to electric shock injuries and/or electrocution.
Recent events (1)
  • — Z (S) $6452

1910.67 C03

Serious Gravity 10 3 instances 4 exposed
Issued
Sep 27, 2024
Abate by
Oct 9, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.67(c)(3): Electrical tests had not been made in conformance with the requirements of ANSI A92.2-1969, Section 5.  (a) Little Bucket Truck: On April 26, 2024 and times prior, employees operated a 2012 Dodge Ram 5500 truck with an insulated Altec aerial lift bucket that had not received dielectric testing, exposing employees to electric shock injuries and electrocution.    (b) Large/Big Bucket Truck: On April 9, 2024 and times prior, employees operated a 2012 International Work Star truck with an insulated Terex Hi-Ranger aerial lift bucket that had not received dielectric testing, exposing employees to electric shock injuries and electrocution.    (c) Tree Bucket Truck: On April 9, 2024 and times prior, employees operated a 2006 GMC C7500 truck with an insulated Altec aerial lift bucket that had not received dielectric testing, exposing employees to electric shock injuries and electrocution.
Recent events (1)
  • — Z (S) $0

View Black Diamond Power Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347388233.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.