OSHA Inspection: AMERICANA ENTERPRISES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AMERICANA ENTERPRISES, INC. in 3302 HARLAN LEWIS ROAD, BELLEVUE, NE 68005 (NAICS 332999). OSHA activity number 347391278.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Americana Enterprises, INC. — free Get an email when a new federal OSHA severe-injury report for Americana Enterprises, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3302 HARLAN LEWIS ROAD
City
BELLEVUE
State
NE
ZIP
68005
Mailing
3302 HARLAN LEWIS ROAD, BELLEVUE, NE 68005
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
125
Ownership type
A

9 citations on file for this inspection.

1910.305 B02 I

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $6,844 · Current $4,791 Reduced
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  On or about April 4th, 2024, employee(s) engaged in material handling and production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska, were exposed to fire and electrical hazards in that the employer failed to ensure live electrical boxes >120 volts were enclosed.  Instances of exposure include but are not limited to:  i.  The cutout box located under the box machine in the docking area did not have a cover that effectively protected the interior wiring. ii.  The outlet box in the assembly area did not have a cover or faceplate that effectively protected the interior wiring.
Recent events (2)
  • — I (S) $4790.8
  • — Z (S) $6844

1910.305 G01 IV A

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $6,844 · Current $4,791 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   On or about April 4, 2024, employee(s) engaged in production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska were exposed to fire and electrical hazards. Multiple flexible extension cords were being used in lieu of permanent wiring by the employee(s). Flexible cords were used provide powering to multiple battery charging stations and cordless hand tools.  Instances of exposure were documented but not limited to:   A.) Flexible cord used and attached to building surface in adjacent storage room across from battery charging stations in the production area.   B.) Flexible cord used and attached to building surface in shipping area.  The flexible cord was powering a ZAP 880 series - 3.
Recent events (2)
  • — I (S) $4790.8
  • — Z (S) $6844

1910.305 G01 IV C

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(C):Flexible cords and cables were used where run through doorways, windows, or similar openings.  On or about April 4th, 2024, employees engaged in production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska 68005, were exposed to fire and electrical hazards. Multiple flexible extension cords were being used and were run through door ways, or other similar openings. The flexible cords were supplying power for various hand tools being used in assembly production area of the facility by employee(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(D):Where attached to building surfaces;  On or about April 4th, 2024, employees engaged in production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska, were exposed to fire and electrical hazards. Multiple flexible extension cords were attached to the building surfaces by tape, tying knots in the cords, and wrapping it around existing conduit. The flexible cords were supplying power for various hand tools being used in assembly production area of the facility by employee(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 II

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $6,844 · Current $4,791 Reduced
29 CFR  1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:  On or about April 4th, 2024, employees engaged in material handling and production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska were exposed to fire and electrical hazards. Employee(s) were exposed to two extension cords that were plugged into the box wrap machine, these cords were spliced in three sperate locations.
Recent events (2)
  • — I (S) $4790.8
  • — Z (S) $6844

1910.334 A02 I

Serious Gravity 1 1 instance 4 exposed
Issued
May 28, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(2)(i):Portable cord and plug connected equipment and flexible cord sets (extension cords) shall be visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket). Cord and plug connected equipment and flexible cord sets (extension cords) which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated.  On or about April 4th, 2024, employees engaged in material handling and production operations in the facility located at 3302 Harlan Lewis Road, Bellevue, Nebraska, were exposed to fire and electrical hazards. Two extension cords were plugged into the box wrap machine and had not been inspected prior to use by the employee(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 E01

Serious Gravity 1 1 instance 1 exposed
Issued
May 28, 2024
Abate by
Jun 24, 2024
Penalty
Initial $6,844 · Current $4,791 Reduced
29 CFR  1910.1200(e)(1):Employers shall develop, implement, and maintain at each workplace, a written hazard communication program which at least describes how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, safety data sheets, and employee information and training will be met, and which also includes the following:  On or about April 4th 2024, , employee(s) engaged in maintenance and production operations located at 3302 Harlan Lewis Road, Bellevue, Nebraska,  were exposed to hazardous chemicals.   The employer failed to develop a written Hazardous Communication Program that consisted of all the required elements.  The following chemicals were documented but not limited to:   A.) Acetone B.) Engine oils C.) Rust off compounds D.) Spray paints E.) Greases  F.) Lubricants
Recent events (2)
  • — I (S) $4790.8
  • — Z (S) $6844

1910.1200 E01 I

Serious Gravity 1 1 instance 1 exposed
Issued
May 28, 2024
Abate by
Jun 24, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(e)(1)(i):The employer did not compile a list of the hazardous chemicals known to be present using a product identifier that was referenced on the appropriate safety data sheet.  On or about  April 4th, 2024 , employee(s) engaged in maintenance and production operations located at 3302 Harlan Lewis Road, Bellevue, Nebraska, were exposed to hazardous chemicals. The employer failed to develop and or provide master chemical list of chemicals.   The following chemicals were documented but not limited to:   A.) Acetone B.) Engine oils C.) Rust off compounds D.) Spray paints E.) Greases  F.) Lubricants
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 L

Repeat Gravity 10 1 instance 2 exposed
Issued
May 28, 2024
Abate by
Jun 24, 2024
Penalty
Initial $31,939 · Current $22,357 Reduced
29 CFR  1910.178(l):Operators were not trained in the safe operation of powered industrial trucks:  On or about April 4th, 2024, at least two employee(s) engaged in material handling operations located at 3302 Harlan Lewis Road, Bellevue, Nebraska, were exposed to struck-by hazards.  The employer failed to ensure that employee(s) received forklift training prior to operating Clark forklift models S30G and TMX25 at the facility.   Americana Enterprises, Inc was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.178(l), which was contained in OSHA inspection number 1687494, citation number 1, item number 1and was affirmed as a final order on 10-24-2023, with respect to a workplace located at 3302 Harlan Lewis Road, Bellevue, Nebraska.