TALLAHASSEE, FL ·
OSHA Inspection: ORIGIS ENERGY SERVICES
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ORIGIS ENERGY SERVICES in 7500 SPRINGHILL ROAD, TALLAHASSEE, FL 32301 (NAICS 221114). OSHA activity number 347427023.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ORIGIS ENERGY SERVICES
- Site address
- 7500 SPRINGHILL ROAD
- City
- TALLAHASSEE
- State
- FL
- ZIP
- 32301
- Mailing
- 6500 RIVER PLACE BOULEVARD, AUSTIN, TX 78730
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221114
- Employees
- 3
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1910.269 D02 IV B
- Issued
- Sep 10, 2024
- Penalty
- Initial $11,292 · Current $6,775 Reduced
General-duty citation text
29 CFR 1910.269(d)(2)(iv)(B): The procedure did not clearly and specifically outline the procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy: a. At Onward Energy?s Solar Powered Farm, located at 7500 Springhill Road in Tallahassee Florida; The Employer exposed employees to electrical shock in that linked inverters #1-4 were not shut down prior to working on inverter #1.
Recent events (2)
- · I (S) $6775.2
- · Z (S) $11292
1910.269 L01 II
- Issued
- Sep 10, 2024
- Penalty
- Initial $8,067 · Current $4,840 Reduced
General-duty citation text
29 CFR 1910.269(l)(1)(ii): Only qualified employees did not work in areas containing unguarded, uninsulated energized lines or parts of equipment operating at 50 volts or more. a. At Onward Energy?s Solar Powered Farm, located at 7500 Springhill Road in Tallahassee Florida; The Employer exposed employees to electrical shock in that an unqualified, temporary worker was exposed to live parts operating at 1,453 VDC.
Recent events (2)
- · I (S) $4840.2
- · Z (S) $8067
More inspections in this industry (NAICS 221114)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 347427023.