OSHA Inspection: ORIGIS ENERGY SERVICES

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ORIGIS ENERGY SERVICES in 7500 SPRINGHILL ROAD, TALLAHASSEE, FL 32301 (NAICS 221114). OSHA activity number 347427023.

Watch Origis Energy Services — free Get an email when a new federal OSHA severe-injury report for Origis Energy Services is published. One employer, no account, unsubscribe in one click.
Site address
7500 SPRINGHILL ROAD
City
TALLAHASSEE
State
FL
ZIP
32301
Mailing
6500 RIVER PLACE BOULEVARD, AUSTIN, TX 78730
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221114
Employees
3
Ownership type
A

2 citations on file for this inspection.

1910.269 D02 IV B

Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $11292.00 · Current $6775.00 Reduced
29 CFR  1910.269(d)(2)(iv)(B): The procedure did not clearly and specifically outline the procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:   a. At Onward Energy?s Solar Powered Farm, located at 7500 Springhill Road in Tallahassee Florida; The Employer exposed employees to electrical shock in that linked inverters #1-4 were not shut down prior to working on inverter #1.
Recent events (2)
  • — I (S) $6775.2
  • — Z (S) $11292

1910.269 L01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $8067.00 · Current $4840.00 Reduced
29 CFR 1910.269(l)(1)(ii): Only qualified employees did not work in areas containing unguarded, uninsulated energized lines or parts of equipment operating at 50 volts or more.   a. At Onward Energy?s Solar Powered Farm, located at 7500 Springhill Road in Tallahassee Florida; The Employer exposed employees to electrical shock in that an unqualified, temporary worker was exposed to live parts operating at 1,453 VDC.