EAU CLAIRE, WI —
OSHA Inspection: DRYLOCK TECHNOLOGIES, LTD.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of DRYLOCK TECHNOLOGIES, LTD. in 3921 NORTH HASTINGS WAY, EAU CLAIRE, WI 54703 (NAICS 322291). OSHA activity number 347463952.
Where did this inspection happen?
- Establishment
- DRYLOCK TECHNOLOGIES, LTD.
- Site address
- 3921 NORTH HASTINGS WAY
- City
- EAU CLAIRE
- State
- WI
- ZIP
- 54703
- Mailing
- 3921 NORTH HASTINGS WAY, EAU CLAIRE, WI 54703
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322291
- Employees
- 298
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.137 C02 VIII
- Issued
- Abate by
- Penalty
- Initial $11754.00 · Current $8228.00 Reduced
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and/or the maximum intervals between tests were not conducted in accordance with Table I-4 and Table I-5: (a) Production area; On or about May 6, 2024, and dates prior, the employer did not ensure the class 0 electrical gloves issued to authorized employees were tested to the voltage listed in Table I-4 and did not follow the testing intervals listed in Table I-5.
Recent events (2)
- — I (S) $8227.8
- — Z (S) $11754
1910.333 A01
- Issued
- Abate by
- Penalty
- Initial $9795.00 · Current $6857.00 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: (a) Throughout the production area; On or about May 6, 2024, and dates prior, the employees working on 24V DC energized electrical equipment were exposed to the hazards of adjacent equipment and conductors, energized from 120V AC up to 480V AC, inside the same electrical cabinets.
Recent events (2)
- — I (S) $6856.5
- — Z (S) $9795
1910.147 C06 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: (a) EAP2; On or about May 6, 2024, and dates prior, the employer did not conduct a periodic inspection of the energy control procedures for the EAP2 adult incontinence production line at least annually to ensure the procedures were effective and conformed to the OSHA standards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at DRYLOCK TECHNOLOGIES, LTD.
EAU CLAIRE, WI—2023-05-17 00:00:00
DRYLOCK TECHNOLOGIES, LTD.
EAU CLAIRE, WI—2023-02-28 00:00:00
DRYLOCK TECHNOLOGIES, LTD.
EAU CLAIRE, WI—2019-02-28 00:00:00
DRYLOCK TECHNOLOGIES, LTD.
View DRYLOCK TECHNOLOGIES, LTD.'s full OSHA safety record →
More inspections in this industry (NAICS 322291)
BOYERTOWN, PA—2026-06-04
BERK INTERNATIONAL, LLC
OGDEN, UT—2026-06-01
KIMBERLY-CLARK WORLDWIDE INC
FORT EDWARD, NY—2026-03-11
IRVING CONSUMER PRODUCTS INC.
COLDWATER, OH—2026-02-24
HEALTH CARE PRODUCTS, INC.
PROSPERITY, SC—2026-02-10
77257 - GEORGIA PACIFIC WOOD PRODUCTS LLC
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC
FRANKLIN, WI—2026-07-10
EDGE BROADBAND SOLUTIONS LLC
APPLETON, WI—2026-07-10
LAWRENCE UNIVERSITY OF WISCONSIN
KIMBERLY, WI—2026-07-10
ENRIQUE RESENDIC
SLINGER, WI—2026-07-10
DYLAN MATTHEW SHELLEY LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347463952.